Appendix No. 26<br />

to Certificate of <strong>Co</strong>nformity:<br />

Terminal conten! of enc10sure type:<br />

Enclosure dimension in mrn:<br />

<strong>KEMA</strong> 99A TEX7540 X<br />

NexT 765016<br />

H: 762 W: 508<br />

D= 160<br />

<strong>KEMA</strong> ='<<br />

~310.6812AR AmIlIm<br />

Postbus9035.NL-6800ET Amhllftl<br />

The lable shows the maximum number of conduclors depending on the cable size and pennitted<br />

current for the above mentioned enclosure.<br />

"<strong>Co</strong>nductor" roeans every conductor entering the enc10sure and every internal connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

Note;<br />

1.5 2.5<br />

86 335<br />

50 97<br />

24 55 106<br />

16 41 103<br />

6 33 85<br />

11 39<br />

15<br />

n Detar lze mrn<br />

10 16 25 35 50 70 95 120 150 185 240<br />

141<br />

44 157<br />

19 41<br />

2 17 42<br />

14 37<br />

13<br />

The terminal content in this 5<br />

area requires apower<br />

dissipation test repor/ from<br />

the manufacturer<br />

In this area yau can add as many<br />

terminals as physically possible.<br />

32 99<br />

18 39<br />

9 23 49<br />

5 14 29<br />

6 20<br />

3<br />

Maximum physical terminal content depends on the terminal dimension and<br />

the maximum pennissible cable size used.<br />

Maximum pennissible rated eurrent of the applied terminals and cabJes must be laken<br />

inta account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />

For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de-rating faetors or nominal rated currents in accordanee with<br />

IEC 439 should be used.<br />

Different types ofterminals can be used togetherby utilising the tabu1arvalues proportionally.<br />

Example: <strong>Co</strong>nductor Size Current Number Load

Hooray! Your file is uploaded and ready to be published.