Appendix No. 26<br />
to Certificate of <strong>Co</strong>nformity:<br />
Terminal conten! of enc10sure type:<br />
Enclosure dimension in mrn:<br />
<strong>KEMA</strong> 99A TEX7540 X<br />
NexT 765016<br />
H: 762 W: 508<br />
D= 160<br />
<strong>KEMA</strong> ='<<br />
~310.6812AR AmIlIm<br />
Postbus9035.NL-6800ET Amhllftl<br />
The lable shows the maximum number of conduclors depending on the cable size and pennitted<br />
current for the above mentioned enclosure.<br />
"<strong>Co</strong>nductor" roeans every conductor entering the enc10sure and every internal connecting<br />
conductor. Any cross connections or earth terminals are not counted.<br />
Note;<br />
1.5 2.5<br />
86 335<br />
50 97<br />
24 55 106<br />
16 41 103<br />
6 33 85<br />
11 39<br />
15<br />
n Detar lze mrn<br />
10 16 25 35 50 70 95 120 150 185 240<br />
141<br />
44 157<br />
19 41<br />
2 17 42<br />
14 37<br />
13<br />
The terminal content in this 5<br />
area requires apower<br />
dissipation test repor/ from<br />
the manufacturer<br />
In this area yau can add as many<br />
terminals as physically possible.<br />
32 99<br />
18 39<br />
9 23 49<br />
5 14 29<br />
6 20<br />
3<br />
Maximum physical terminal content depends on the terminal dimension and<br />
the maximum pennissible cable size used.<br />
Maximum pennissible rated eurrent of the applied terminals and cabJes must be laken<br />
inta account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />
For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />
Dissipation Test Report ).<br />
When using the table above, de-rating faetors or nominal rated currents in accordanee with<br />
IEC 439 should be used.<br />
Different types ofterminals can be used togetherby utilising the tabu1arvalues proportionally.<br />
Example: <strong>Co</strong>nductor Size Current Number Load