Appendix No. 14<br />
to Certificate of <strong>Co</strong>nformity:<br />
Terminal content of enclosure type:<br />
Enclosure dimension in mm:<br />
<strong>KEMA</strong>99ATEX7540X<br />
NexT 987420<br />
H= 980 W. 740<br />
D· 205<br />
<strong>KEMA</strong>~<br />
IU.kEMA<br />
Utrechfseweg 310. 8812 AR Amhern<br />
Postbus 9035, Nl-6BOOET Am/lerrl<br />
The table shows the maximum number of conductors depending on the cable size and pennitted<br />
current for the above mentioned enclosure.<br />
"<strong>Co</strong>nductor tl means every conductor entering the enclosure and every internal connecting<br />
conductor. Any cross connections or earth terminals are not counted.<br />
1.5 2.5<br />
364<br />
177<br />
61 118 457<br />
25 69 132<br />
32 75<br />
22<br />
The terminal content in this<br />
area requires apower<br />
dissipation test report from<br />
the manufacturer<br />
on uctor 1Ze rnrn<br />
10 16 25 35 50 70 95 120 150 185 240<br />
144<br />
57 140<br />
8 46 116<br />
15 54<br />
21<br />
192<br />
60<br />
26<br />
2<br />
215<br />
56<br />
23<br />
In this area you can add as many<br />
terminals as physically possible.<br />
57<br />
20 50<br />
18 44 135<br />
7 25 53<br />
13 32 67<br />
6 19 40<br />
9 27<br />
4<br />
Maximum physical terminal content depends on the terminal dimension and<br />
the maximum permissible cable size used.<br />
Note:<br />
Maximum pennissible rated current of the applied terminals and cables must be taken<br />
into account. Cables used intemal1y must be suitable for a temperature between 70° and 80°C.<br />
For larger cables, the number of conductors must be advised hy the manufacturer ( with Power<br />
Dissipation Test Report ).<br />
When using the tahle above, de-rating factors or nominal rated currents in accordance with<br />
IEC 439 should he used.<br />
Different types ofterminals can be used together by utilising the tabular values proportionally.<br />
Example: <strong>Co</strong>nductor Size Current Number Load