Appendix No. 22<br />

to Certificate of <strong>Co</strong>nfonnity: <strong>KEMA</strong> 99ATEX7540 X<br />

Terminal content of enc10sure type:<br />

Enclosure dimension in mrn:<br />

NexT 453816<br />

H= 458 W= 382 D= 160<br />

<strong>KEMA</strong>='<<br />

~="weg 310, 6812 AR Amhem<br />

Postbus 9035. NL-6800 ET Amhlll'l"<br />

Tbc table shows the maximum number of conductors depending on the eable size and permitted<br />

current for the above mentioned enc1osure.<br />

lI<strong>Co</strong>nductor" means every conductor entering the enclosure and every internat connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

Note:<br />

215<br />

104<br />

36 69 270<br />

15 40 78<br />

19 44 85<br />

13 33 83<br />

5 27 69<br />

9 32<br />

12<br />

The terminal content in this<br />

area requires apower<br />

dissipation test reportfrom<br />

the manufacturer<br />

on uctor Ire mrn<br />

10 16 ~ II 50 W ~ IW 150 l~ 2~<br />

113<br />

35 127<br />

15 33<br />

13 34<br />

11 30<br />

10<br />

4<br />

In this area yau can add os many<br />

terminals os physically possible.<br />

26 79<br />

15 31<br />

8 19 39<br />

4 11 23<br />

5<br />

Maximum physical terminal coolent depends on the terminal dimension and<br />

the maximum pennissible cable sire used.<br />

Maximum pennissible rated current of the applied tenninals and cables must be taken<br />

into account. Cables used intemally must be suitable for a temperature between 70° aod 80°C.<br />

For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de-rating factors or nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of tenninals can be used together by utilising the tabular values proportionaUy.<br />

Example: <strong>Co</strong>nductor Size Cuttent Number Load