Appendix No. 28<br />
to Certificate of <strong>Co</strong>nformity:<br />
Terminal content of enclosure type:<br />
Enclosure dimension in mm:<br />
<strong>KEMA</strong> 99ATEX7540 X<br />
NexT 916116<br />
H= 914 W= 610<br />
D= 160<br />
<strong>KEMA</strong> :f(<br />
~310,lI812Nl-<br />
Postbus 9035. Nl-6800 ET Am'*"<br />
The table shows the maximum number of conductors depending on the cable size and permiued<br />
current for the above mentioned enclosure.<br />
"<strong>Co</strong>nductor" means every conductor entering the enclosure and every internal connecting<br />
conductor. Any cross connections or earth terminals are not counted.<br />
1.5 2.5<br />
303<br />
147<br />
50<br />
21<br />
98 379<br />
57 110<br />
27 62<br />
18<br />
120<br />
47 117<br />
7 38<br />
13<br />
10 16<br />
97<br />
45<br />
17<br />
The terminal content in this<br />
area requires apower<br />
dissipation test report /rom<br />
the manufacturer<br />
159<br />
50<br />
21<br />
2<br />
178<br />
47<br />
19<br />
47<br />
16 42<br />
15<br />
5<br />
95 120 150 185 240<br />
In this area you can add as many<br />
terminals as physically possible.<br />
36 112<br />
21 44<br />
11 27 56<br />
5 16 33<br />
7<br />
Maximum physical terminal content depends on the terminal dimension and<br />
the maximum permissible cable size used.<br />
Note:<br />
Maximum pennissible rated current of tbe applied terminals and cabJes must be taken<br />
ioto account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />
For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />
Dissipation Test Report ).<br />
When using the table above. de-rating factors or nominal rated currents in accordance with<br />
IEC 439 should be used.<br />
Different types of terminals can be used together by utilising the tabuJar values proportionally.<br />
Example: <strong>Co</strong>nductor Size Current Number Load