Appendix No. 24<br />

to Certificate of <strong>Co</strong>nformity: <strong>KEMA</strong> 99A TEX7540 X<br />

Terminal content of enc10sure type:<br />

Enclosure dimension in mrn:<br />

NexT 484816<br />

H= 480 W= 480 D= 160<br />

<strong>KEMA</strong>~<br />

N.V.IEMA<br />

__ 31~6812AR Am••••<br />

Postbus 9035. Nl-6800ET Amhent<br />

The table shows the maximum uumber cf conductors depending on the cable size and permitted<br />

current for the above mentioned enc1osure.<br />

"<strong>Co</strong>nductor" means every conductor entering the enclosure and every interna! cOlU1ecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

1.5 2.5<br />

235<br />

114<br />

39 76 294<br />

16 44 85<br />

21 48 93<br />

14 36 90<br />

5 29 75<br />

10 35<br />

13<br />

on nctor lze mm<br />

10 16 25 35 50 70 95 120 150 185 240<br />

In this area yau can add as many<br />

terminals os physically possible.<br />

123<br />

38 138<br />

16 36<br />

14 37<br />

12 32<br />

11 28<br />

The terminal content in (his 4 16<br />

area requires apower 8<br />

dissipation test report from<br />

the manufacturer<br />

87<br />

34<br />

21 43<br />

4 12<br />

Maximum physicaJ terminal content depends on the terminal dimension and<br />

the maximum pennissible cable size used.<br />

Note:<br />

Maximum permissible rated current of the applied terminals and cabtes must be taken<br />

into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />

For larger cooles, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de·rating factors or nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of terminals can be used together by utilising the tabular values proportionally.<br />

Example: <strong>Co</strong>nductor Size Current Number Load