Appendix No. 34<br />

to Certificate of <strong>Co</strong>nformity:<br />

Terminal content of enclosure type:<br />

Enclosure dimension in mm:<br />

<strong>KEMA</strong> 99ATEX7540 X<br />

NexT 916128<br />

H= 914 W= 610<br />

D= 280<br />

<strong>KEMA</strong> :b<br />

u.••••.• ,<br />

Utrachtseweg 310, 6812 AR AmPIenI<br />

Postbus9Q35, Nl-6800ET Arn1\enI<br />

The table shows the maximum number of conducters depending on the cable size and pennitted<br />

current for the above mentioned enclosure.<br />

"<strong>Co</strong>nductor" means every conductor entering the enclosure and every internal connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

Note:<br />

1.5 2.5<br />

120 466<br />

70 135<br />

33 77 147<br />

22 58<br />

8<br />

The terminal content in this<br />

area requires apower<br />

dissipation test report from<br />

the manufacturer<br />

on ucter lze mm<br />

10 16 25 35 50 70 95 120 150 185 240<br />

143<br />

47 119<br />

16 55<br />

21<br />

196<br />

61 219<br />

26 58<br />

2 23<br />

In this area you can add as many<br />

terminals as physica/ly possible.<br />

58<br />

20 51<br />

18 45 138<br />

7 26 54<br />

13 33 68<br />

7 20 41<br />

9 28<br />

4<br />

Maximum physical terminal content depends on the terminal dimension and<br />

the maximum permissible cable size used.<br />

Maximum permissib1e rated current of the applied terminals and cabJes must be laken<br />

into account. Cables used intemaUy must be suitable for a temperature between 70° and 80°C.<br />

For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de-rating factors er nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of terminals can be used together by utilising the tabular values proportionaUy.<br />

Example: <strong>Co</strong>nductor Size Current Number Load