Appendix No. 12<br />

10 Certificate of <strong>Co</strong>nformily:<br />

Terminal content of enclosure Iype:<br />

Enclosure dimension in mm:<br />

<strong>KEMA</strong> 99ATEX7540 X<br />

NexT 866420<br />

H= 860 W- 640 D- 205<br />

Tbe table shows the maximum number of conduclors depending on the cable size and permitted<br />

currenl for the above menlioned enc1osure.<br />

"<strong>Co</strong>nductor" means every conductor entering the enc10sure and every internal connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

Current 1.5 2.5<br />

(Amps)<br />

332<br />

161<br />

55 107 416<br />

23 62 121<br />

30 68<br />

20<br />

132<br />

51 128<br />

7 42<br />

14<br />

The terminal content in this<br />

area requires apower<br />

dissipation test report from<br />

the manufacturer<br />

10 95 120 150 185 240<br />

106<br />

49<br />

19<br />

175<br />

55<br />

23<br />

2<br />

196<br />

51<br />

21<br />

In this area you can add as many<br />

terminals as physically possible.<br />

52<br />

18 46<br />

16 40 123<br />

6 23 48<br />

12 29 61<br />

6 17 36<br />

8 25<br />

3<br />

Maximum physical terminal content depends on the terminal dimension and<br />

the maximum pennissible cable size used.<br />

Note:<br />

Maximum permissible raled current of the applied terminals and cables must be taken<br />

into account. Cables used intemally must be suitable for a temperature between 70° and gO°C.<br />

For targer cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Repon ).<br />

When using the table above, de-rating factors or nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of terminals can be used together by utilising the tabular values proportionally.<br />