Appendix No. 12<br />
10 Certificate of <strong>Co</strong>nformily:<br />
Terminal content of enclosure Iype:<br />
Enclosure dimension in mm:<br />
<strong>KEMA</strong> 99ATEX7540 X<br />
NexT 866420<br />
H= 860 W- 640 D- 205<br />
Tbe table shows the maximum number of conduclors depending on the cable size and permitted<br />
currenl for the above menlioned enc1osure.<br />
"<strong>Co</strong>nductor" means every conductor entering the enc10sure and every internal connecting<br />
conductor. Any cross connections or earth terminals are not counted.<br />
Current 1.5 2.5<br />
(Amps)<br />
332<br />
161<br />
55 107 416<br />
23 62 121<br />
30 68<br />
20<br />
132<br />
51 128<br />
7 42<br />
14<br />
The terminal content in this<br />
area requires apower<br />
dissipation test report from<br />
the manufacturer<br />
10 95 120 150 185 240<br />
106<br />
49<br />
19<br />
175<br />
55<br />
23<br />
2<br />
196<br />
51<br />
21<br />
In this area you can add as many<br />
terminals as physically possible.<br />
52<br />
18 46<br />
16 40 123<br />
6 23 48<br />
12 29 61<br />
6 17 36<br />
8 25<br />
3<br />
Maximum physical terminal content depends on the terminal dimension and<br />
the maximum pennissible cable size used.<br />
Note:<br />
Maximum permissible raled current of the applied terminals and cables must be taken<br />
into account. Cables used intemally must be suitable for a temperature between 70° and gO°C.<br />
For targer cables, the number of conductors must be advised by the manufacturer ( with Power<br />
Dissipation Test Repon ).<br />
When using the table above, de-rating factors or nominal rated currents in accordance with<br />
IEC 439 should be used.<br />
Different types of terminals can be used together by utilising the tabular values proportionally.<br />
Example: <strong>Co</strong>nductor Size eurrent Number Load