AppendixNo. 30<br />
to Cenificate of <strong>Co</strong>nformity:<br />
Terminal content of encJosure type:<br />
Enclosure dimension in mm:<br />
<strong>KEMA</strong>99ATEX7540X<br />
NexT 1056120<br />
H- 1050 W- 610<br />
1be tabJe shows the maximum number of conductors depending on the cable size and pennined<br />
current far the above mentioned enclosure.<br />
·'<strong>Co</strong>nductor" means every conductor entering the enclosure and every internal connecting<br />
conductor. Any cross connections or eanh tenninals are not counted.<br />
1.5 2.5<br />
]08 420<br />
63 122<br />
30 69 133<br />
20 52 129<br />
7 42<br />
14<br />
'I'M terminal contenl in Ihis<br />
area requires apower<br />
dissipation test reportfrom<br />
the manufacturer<br />
on uetor lze mm<br />
10 16 25 35 50 70 95 120 150 185 240<br />
107<br />
50<br />
19<br />
176<br />
55<br />
23<br />
2<br />
197<br />
52<br />
21<br />
["this area you can add as many<br />
terminals as physically possibIe.<br />
53<br />
18 46<br />
16 40 124<br />
6 23 49<br />
12 29 62<br />
6 18 37<br />
8 25<br />
3<br />
Maximum physical terminal content depends on the terminal dimension and<br />
the maximum permissible cable size used.<br />
Note:<br />
Maximum pennissible rated current of the applied tenninals and cables must be laken<br />
into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />
For largeT cables, the number of conduetors must be advised by the manufacturer ( with Power<br />
Dissipation Test Report ).<br />
When using the table above, de-rating factors or nominal rated currents in accordance with<br />
IEC 439 should be used.<br />
Different types of terminals can be used together by utiJising the tabular values proportionally.<br />