AppendixNo. 30<br />

to Cenificate of <strong>Co</strong>nformity:<br />

Terminal content of encJosure type:<br />

Enclosure dimension in mm:<br />

<strong>KEMA</strong>99ATEX7540X<br />

NexT 1056120<br />

H- 1050 W- 610<br />

1be tabJe shows the maximum number of conductors depending on the cable size and pennined<br />

current far the above mentioned enclosure.<br />

·'<strong>Co</strong>nductor" means every conductor entering the enclosure and every internal connecting<br />

conductor. Any cross connections or eanh tenninals are not counted.<br />

1.5 2.5<br />

]08 420<br />

63 122<br />

30 69 133<br />

20 52 129<br />

7 42<br />

14<br />

'I'M terminal contenl in Ihis<br />

area requires apower<br />

dissipation test reportfrom<br />

the manufacturer<br />

on uetor lze mm<br />

10 16 25 35 50 70 95 120 150 185 240<br />

107<br />

50<br />

19<br />

176<br />

55<br />

23<br />

2<br />

197<br />

52<br />

21<br />

["this area you can add as many<br />

terminals as physically possibIe.<br />

53<br />

18 46<br />

16 40 124<br />

6 23 49<br />

12 29 62<br />

6 18 37<br />

8 25<br />

3<br />

Maximum physical terminal content depends on the terminal dimension and<br />

the maximum permissible cable size used.<br />

Note:<br />

Maximum pennissible rated current of the applied tenninals and cables must be laken<br />

into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />

For largeT cables, the number of conduetors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de-rating factors or nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of terminals can be used together by utiJising the tabular values proportionally.<br />

Example: <strong>Co</strong>nductor Siu eurren. Number Load