Appendix No. 18<br />

to Certificate of <strong>Co</strong>nformity:<br />

Terminal content of enc10sure type:<br />

Endosure dimension in rum:<br />

<strong>KEMA</strong> 99ATEX7540 X<br />

NexT 1903020<br />

H~ 1900 W; 300<br />

D: 205<br />

<strong>KEMA</strong> =!<<br />

•• V. <strong>KEMA</strong><br />

UtredrtSeweg310.6812AR AmhIm<br />

'nstbus9035.Nl-6800ET Am_<br />

The table shows the maximum number of conductors depending on the cable size and permitted<br />

current for the above rnentioned enclosure.<br />

"<strong>Co</strong>nductor" means every conductor entering the enc10sure and every internal connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

1.5 2.5<br />

The terminal content in this<br />

area requires apower<br />

dissipation test reportfrom<br />

the manufacturer<br />

onductor ,slze {mm<br />

10 16 25 35 50 70 95 120 150 185 240<br />

In this area you can add as many<br />

terminals as physically possible.<br />

116<br />

36 I 130<br />

i5T34<br />

~ 12 30<br />

11 26 81<br />

4 15 32<br />

8 19<br />

"4<br />

Maximum physical terminal content depends on the terminal dimension and<br />

the maximum pennissible cable size used.<br />

40<br />

TI 24<br />

5"<br />

Note:<br />

Maximum permissible rated current of the applied terminals and cables must be taken<br />

into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />

For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report).<br />

When using the tahle above, de-rating factors or nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of terminals can be used together by utilising the tabular values proportionally.<br />

Example: <strong>Co</strong>nductor Size Current Number Load