Appendix No. 18<br />
to Certificate of <strong>Co</strong>nformity:<br />
Terminal content of enc10sure type:<br />
Endosure dimension in rum:<br />
<strong>KEMA</strong> 99ATEX7540 X<br />
NexT 1903020<br />
H~ 1900 W; 300<br />
D: 205<br />
<strong>KEMA</strong> =!<<br />
•• V. <strong>KEMA</strong><br />
UtredrtSeweg310.6812AR AmhIm<br />
'nstbus9035.Nl-6800ET Am_<br />
The table shows the maximum number of conductors depending on the cable size and permitted<br />
current for the above rnentioned enclosure.<br />
"<strong>Co</strong>nductor" means every conductor entering the enc10sure and every internal connecting<br />
conductor. Any cross connections or earth terminals are not counted.<br />
1.5 2.5<br />
The terminal content in this<br />
area requires apower<br />
dissipation test reportfrom<br />
the manufacturer<br />
onductor ,slze {mm<br />
10 16 25 35 50 70 95 120 150 185 240<br />
In this area you can add as many<br />
terminals as physically possible.<br />
116<br />
36 I 130<br />
i5T34<br />
~ 12 30<br />
11 26 81<br />
4 15 32<br />
8 19<br />
"4<br />
Maximum physical terminal content depends on the terminal dimension and<br />
the maximum pennissible cable size used.<br />
40<br />
TI 24<br />
5"<br />
Note:<br />
Maximum permissible rated current of the applied terminals and cables must be taken<br />
into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />
For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />
Dissipation Test Report).<br />
When using the tahle above, de-rating factors or nominal rated currents in accordance with<br />
IEC 439 should be used.<br />
Different types of terminals can be used together by utilising the tabular values proportionally.<br />
Example: <strong>Co</strong>nductor Size Current Number Load