Appendix No. 20<br />

to Certificate of <strong>Co</strong>nfonnity:<br />

Terminal conten! cf enclosure type:<br />

Enclosure dimension in mrn:<br />

<strong>KEMA</strong> 99ATEX7S40 X<br />

NexT 303016<br />

H= 306 W= 306 D= 160<br />

The table shows the maximum number of conductors depending on the cable size and pennitted<br />

current for the above mentioned enclosure.<br />

"<strong>Co</strong>nductor" means every conductor entering the enclosure and every internal connecting<br />

conductor. Any cross connections or earth terminals are not counted.<br />

1.5 2.5<br />

184<br />

89<br />

30 59 230<br />

12 34 67<br />

16 38 73<br />

11 28 71<br />

4 23 58<br />

7 27<br />

10<br />

The terminal content in this<br />

area requires apower<br />

dissipation test report from<br />

the manufacturer<br />

on ucter tze mrn<br />

10 16 25 35 50 70 95 120 150 185 240<br />

96<br />

30 108<br />

13 28<br />

11 29<br />

10<br />

In this area you can add as many<br />

terminals as physically possible.<br />

Maximum physical terminal conten! depends on the terminal dimension and<br />

the maximum pennissible coole size used.<br />

Note:<br />

Maximum pennissible rated current of the applied terminals and cables must be taken<br />

into account. Cables used intemally must be suitable for a temperature between 70° and 80°C.<br />

For larger cables, the number of conductors must be advised by the manufacturer ( with Power<br />

Dissipation Test Report ).<br />

When using the table above, de-rating factors or nominal rated currents in accordance with<br />

IEC 439 should be used.<br />

Different types of tenninals can be used together by utilising the tabular values proportionaJly.<br />

Example: <strong>Co</strong>nductor Size Current Number Load