(20) LCD Language displayed selection (Sn-25)Sn-25 = 0EnglishSn-25 = 1Chinese(21) Multi-Function Analog Output A01 Function Selection (Sn-26)(22) Multi-Function Analog Output A02 Function Selection (Sn-27)The multi-function analog output A01 and A02 can be set to monitor the following 11status items as shown below:Sn-26, Sn-27SettingMonitored Contents (LCD Display)Input0 Frequency Command 0 ~ max. frequency1 Output Frequency 0 ~ max. frequency2 Output Current 0 ~ rated Current3 Output Voltage 0 ~ rated Voltage4 DC Voltage220V: 0 ~ 400VDC440V: 0 ~ 800VDCDescriptionOutput5 Output Power0 ~ max. applicable motorcapacity0 ~ 10V10 Comm. Control 0 ~ 100%* 16 VIN Analog Command 0 ~ 10V7 AIN Analog Command 4 – 20mA8 AUX Analog Command 0 ~ 10V9 PID detected value (VIN + AIN) 0 ~ 10VThe output gain Bn-11, Bn-12 will determine the output voltage at multi-functionanalog output at A01 and A02 terminal. The specified multiple of 10V will correspondto the 100% output monitored value.*1When Sn-26 ~ Sn-27=10, the multi-function output terminals A01, A02 are controlledby RS-485 commutation. Please ref. To “7300PA MODBUS/PROFIBUS applicationmanual”.(23) Not Used (Sn-28)(24) Not Used (Sn-29)102