(37) Auto Restart Time Interval (Cn-62)Set the auto reset / restart operation time interval when the number of auto reset /restart operation is more then 2.The setting range of Cn-62 is 0~20 sec, the auto restart time interval is minimumbaseblock time (Cn-40) when the setting value of Cn-62 is 0. The auto restart time interval is the setting value of Cn-40 when the setting valueof Cn-62 < Cn-40. The auto restart time interval is the setting value of Cn-62 when the setting valueof Cn-62 > Cn-40.(38) <strong>Motor</strong> Overheat Protection Time (Cn-63)Time delay for motor overheat protection when the detected temperature of PTCthermistor motor temperature sensor reached the trip level.Generally, it is not needed to change the set value of Cn-63, The factory setting is150%, 1 minutes motor overheat capability. Refer to motor overheat protectionsetting of Sn-19.63