12.07.2015 Views

ABB i-bus® EIB Room thermostat solo®, FM Type: 6124-xx

ABB i-bus® EIB Room thermostat solo®, FM Type: 6124-xx

ABB i-bus® EIB Room thermostat solo®, FM Type: 6124-xx

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>ABB</strong> i-bus ® <strong>EIB</strong><strong>Room</strong> <strong>thermostat</strong> solo ® , <strong>FM</strong><strong>Type</strong>: <strong>6124</strong>-<strong>xx</strong>ParametersThe default setting for the valuesis printed in bold type.Manual setpoint selection:– Range for manual setpoint selection disabled+/– 1 K+/– 3 K+/– 5 KOnly for manual selection:– Maximum increase of setpoint 0 K / 1 K / 2 K / 3 K / 4 K / 5 Kfor heating– Maximum reduction of setpoint 0 K / 1 K / 2 K / 3 K / 4 K / 5 Kfor cooling– Exp.: Range for setpoint selection:+/– 5KMax. increase in heating: 3 K Setting range for heating –5K to +3KMax. reduction in cooling: 1 K Setting range for cooling –1K to +5K– Behaviour on receipt of a manual setpoint selection unchangedbase setpointreset manual setpoint selectionMarch 2003 2 - 13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!