InfeedLine contactor controlCommissioning steps: Connect the line contactor control contact to DI/DO 8.NoteNote the current carrying capacity of the digital output (see the EquipmentManual). A line contactor may have to be used. Parameterize DI/DO 8 as an output (p728.8 = 1). Assign p0738 the control signal for the line contactor r0863.1. Connect the line contactor feedback contact to DI/DO 9. Assign p0860 an inverted input signal r0723.9. Enter the monitoring time for the line contactor (100 ms) in p0861.<strong>Functi</strong>on diagram overview (refer to the List Manual) 8934 Missing enable signals, line contactor controlParameter overview (see List Manual) r0863.1 CO/BO: Drive coupling status word/control word p0860 BI: Line contactor, feedback signal© Siemens AG 2006 All Rights Reserved<strong>SINAMICS</strong> <strong>S120</strong> <strong>Functi</strong>on Manual, 03/2006 Edition1-39