22.4<strong>Metering</strong> <strong>Devices</strong>, <strong>Protective</strong> <strong>Relays</strong>, <strong>Software</strong> <strong>and</strong> Connectivity<strong>Protective</strong> <strong>Relays</strong>222222222222222222222222222222222222222222222222222222222222Protection Elements TolerancesNotice: The tripping delay relates to the time between alarm<strong>and</strong> trip. The tolerance of the operating time relates to the timebetween when the measured value has exceeded the thresholduntil the protection element is picked up.DescriptionToleranceDifferential Protection Stages: 87[x]Id > 0.1 Id[x]±3% of the setting value resp. 1% I nOperating time Id > 0.3 x I n < 35 msId > 0.5 x I n < 25 msId > 1.5 x I n < 20 msGround Differential Protection Stages: 87GD[x]Id > 0.1 Id[x]±3% of the setting value resp. 1% I nOperating time Ide > 0.3 x I n < 35 msIde > 0.5 x I n < 25 msIde > 1.5 x I n < 20 msOvercurrent Protection Elements: 50P[x], 51P[x]Pickup±1.5% of the setting value resp. 1% I nResetting ratio97% or 0.5% x I ntDEFT±1% resp. ±10 msOperating time Starting from I higherthan 1.1 x I>