13.07.2015 Views

Brunner USA Instructions - Robeys Ltd

Brunner USA Instructions - Robeys Ltd

Brunner USA Instructions - Robeys Ltd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Ventilation systems, fume hoods, kitchen fans, etc. with a powerconsumption of more than 2A must not be connected directly to the<strong>USA</strong>.There must be a power contactor installed.This contactor is part of thesafety device and must meet therequirements of EN 50165-1 (ie60947 and contactors must bedesigned by a mechanical life3x106 switching cycles haveEN).Welding of the contacts to protectagainst a backup is required,which reduces the maximumpermissible switching current ofthe contactor to the 0.6 times. Anexample of such a circuit isshown in the picture.Relay is open. When stove is in operationand under pressure to low air contact ismadeSchematic diagram show connection formultiple fans.<strong>Brunner</strong> <strong>USA</strong> Installation & Operation Manual 13August 2013

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!