Curves (continued)<br />
Connection interfaces 0<br />
Advantys Telefast ABE 7 pre-wired system<br />
Connection sub-bases for <strong>Twido</strong> <strong>controller</strong><br />
Electrical durability (in millions of operating cycles, conforming to IEC 60947-5-1)<br />
ABE 7B20MRM20 and ABE 7E16SRM20<br />
d.c. loads<br />
DC 12 curves (1) DC 13 curves (2)<br />
Millions of<br />
operating cycles<br />
0,50<br />
0,45<br />
0,40<br />
230V<br />
0,35<br />
110V<br />
0,30<br />
0,25<br />
0,20<br />
48V<br />
0,15<br />
0,10<br />
0,05<br />
0,00<br />
0,25 0,50<br />
0,75 1 1,25<br />
1,50<br />
1,75<br />
2<br />
Current A<br />
Millions of<br />
operating cycles<br />
2,0<br />
1,8<br />
1,6<br />
1,4<br />
1,2<br />
1,0<br />
0,8<br />
230V<br />
110V<br />
48V<br />
0,6<br />
24V<br />
0,4<br />
0,2<br />
0,0<br />
0 0,2<br />
0,4 0,6<br />
0,8<br />
1<br />
Current A<br />
a.c. loads<br />
AC 12 curves (3) AC 14 curves (4)<br />
Millions of<br />
operating cycles<br />
1,50<br />
1,25<br />
1,00<br />
0,75<br />
0,50<br />
0,25<br />
0,00<br />
0<br />
0,5<br />
24V<br />
48V<br />
110V<br />
230V<br />
1 1,5<br />
2<br />
Current A<br />
Millions of<br />
operating cycles<br />
1,0<br />
0,9<br />
0,8<br />
0,7<br />
0,6<br />
0,5<br />
0,4<br />
0,3<br />
0,2<br />
0,1<br />
0,0<br />
0<br />
L/R = 10ms 48V<br />
L/R = 10ms 24V<br />
L/R = 60ms 48V<br />
L/R = 60ms 24V<br />
0,2 0,4 0,6<br />
0,8<br />
1<br />
Current A<br />
AC 15 curves (5)<br />
Millions of<br />
operating cycles<br />
1,0<br />
0,9<br />
0,8<br />
0,7<br />
0,6<br />
0,5<br />
0,4<br />
0,3<br />
0,2<br />
0,1<br />
0,0<br />
0<br />
0,5<br />
24V<br />
48V<br />
1 1,5<br />
2<br />
Current A<br />
(1) DC 12: control of resistive loads and of solid state loads isolated by optocoupler, L/R ≤ 1 ms.<br />
(2) DC 13: control of electromagnets, L/R ≤ 2 x (Ue x Ie) in ms, Ue: Rated operational voltage, Ie: rated operational current (with a protective diode on the load, DC12<br />
curves must be used with a coefficient of 0.9 applied to the number in millions of operating cycles)<br />
(3) AC 12: control of resistive loads and of solid state loads isolated by optocoupler, cos ϕ ≤ 0.9.<br />
(4) AC 14: control of small electromagnetic loads ≤72 VA, make: cos ϕ = 0.3, break: cos ϕ = 0.3.<br />
(5) AC 15: control of electromagnetic loads > 72 VA, make: cos ϕ = 0.7, break: cos ϕ = 0.4.<br />
Presentation :<br />
page 96<br />
Compatibility :<br />
page 97<br />
Characteristics :<br />
pages 98 and 99<br />
References, dimensions :<br />
pages 102 and 103<br />
Schemes :<br />
pages 104 to 107<br />