Cabling system<br />

Modicon Premium<br />

automation platform 0<br />

AS-Interface cabling system<br />

1<br />

AS-Interface fl at cables are available in two versions, yellow and black, according to<br />

the type of application: standard and TPE (resistant to splashing oil and to<br />

environments with petrol vapours). Various tap junctions are available to meet all<br />

cabling needs. They have a degree of protection of IP 67.<br />

AS-Interface infrastructure<br />

2<br />

Modicon<br />

Premium<br />

TSX SAY 1000<br />

<strong>Twido</strong><br />

TWD NOI 10M3<br />

3<br />

Phaseo<br />

ASI ABL M3024<br />

TeSys U<br />

ASI LUF C5E<br />

Advantys IP 67 I/O<br />

ASI 67FMP22E<br />

2 2 7<br />

4<br />

5<br />

1 Advantys IP 67 I/O<br />

ASI 67FFB03<br />

1 6<br />

6<br />

5<br />

1<br />

Advantys IP 20 I/O<br />

ASI 20MT41E<br />

3<br />

6<br />

Installation<br />

AS-Interface cable lengths<br />

We recommend use of the fl at yellow cable. The maximum length of an AS-Interface<br />

segment is 100 m, which can be extended to:<br />

b 200 m by using a repeater or a line extension:<br />

M<br />

A<br />

4<br />

A<br />

7<br />

S S S S<br />

100 m 100 m<br />

8<br />

b 300 m with 2 repeaters.<br />

b 500 m by placing the master in the centre of the network:<br />

A 4 A 4 M<br />

A<br />

4 A 4<br />

A<br />

9<br />

10<br />

S S S<br />

S<br />

S<br />

S<br />

S<br />

S<br />

S S S S<br />

100 m 100 m 50 m 50 m 100 m 100 m<br />

M = Master Module<br />

A = Supply<br />

S = Interface or component<br />

Note: 300 m corresponds to the maximum distance between the master and the furthermost<br />

slave.<br />

For more information on the installation of AS-Interface, please refer to section 5 of<br />

our “Machines and Installations with Industrial Communications” catalogue.<br />