Functions<br />

<strong>Twido</strong> programmable <strong>controller</strong> 0<br />

Asynchronous serial links<br />

Modbus and character mode protocols<br />

Modbus serial link<br />

<strong>Twido</strong> (master)<br />

TeSys U<br />

TeSys U<br />

<strong>Twido</strong> slave<br />

Magelis XBT N<br />

The Modbus serial link meets the needs of<br />

master/slave architectures (it is nevertheless<br />

necessary to check that the Modbus services<br />

required for the application are implemented on the<br />

devices concerned).<br />

Modbus link<br />

Zelio Logic<br />

Advantys<br />

Advantys<br />

OTB OTB<br />

Preventa XPS MC<br />

ATV 31<br />

The bus consists of a master station and slave<br />

stations. Only the master station can initiate the<br />

exchange (direct communication between slave<br />

stations is not possible). Two exchange methods are<br />

possible:<br />

bQuestion/reply, questions from the master are<br />

addressed to a speci c slave. The master waits for<br />

the reply to be returned by the slave polled.<br />

b Distribution, the master distributes a message to all<br />

the slave stations on the bus. These stations execute<br />

the instruction without sending a reply.<br />

Modbus and character mode characteristics<br />

Protocol Modbus Character mode<br />

Structure Type Non isolated serial link (1)<br />

Access method Master/slave type –<br />

Physical interface RS 232, 3-wire RS 485, 3-wire RS 232, 3-wire RS 485, 3-wire<br />

Transmission Mode Asynchronous in basic band<br />

Frame RTU/ASCII, Half duplex Full duplex Half duplex<br />

Binary rate 0.3…38.4 Kbit/s (default 19.2 Kbit/s) 0.3…38.7 Kbit/s (default 19.2 Kbit/s)<br />

Format<br />

7 or 8 data bits, 1 or 2 stop bits<br />

Parity<br />

Without, even or odd<br />

Medium Shielded twisted pair Single or double Shielded twisted pair<br />

shielded twisted pair<br />

Configuration Number of devices 2 (point to point) 32 max per segment 2 (point to point) 32 max per segment<br />

Max. number of link addresses 244 248<br />

Max. length of bus (1) 15 m 10 m not isolated<br />

1000 m isolated (2)<br />

Max. length of a tap link – 10 m not isolated<br />

30 m isolated(2)<br />

Services Frame 250 bytes of data per request<br />

15 m 10 m not isolated<br />

1000 m isolated (2)<br />

– 10 m not isolated<br />

30 m isolated(2)<br />

Security, check parameter<br />

One CRC on each frame (RTU)<br />

One LRC on each frame (ASCII)<br />

One LRC on each frame (ASCII)<br />

Monitoring Diagnostic counters, event counters –<br />

Modbus functions<br />

Modbus functions available on <strong>Twido</strong> <strong>controller</strong> serial link Code Modbus slave (server) Modbus master (client)<br />

01 Read n internal bits %M Read output bits<br />

02 Read n internal bits %M Read input bits<br />

03 Read n internal words %MW Read words<br />

04 Read n internal words %MW Read input words<br />

05 Write 1 internal bit %M Write 1 bit or n bits<br />

06 Write 1 internal word %MW Write 1 word or n words<br />

15 Read n internal bits %M Write n output bits<br />

16 Write n internal words %MW Write n output words<br />

23 Read or write n internal words %MW, –<br />

only with 40 I/O compact base <strong>controller</strong><br />

TWD LCpp 40DRF<br />

43 Read device identi cation –<br />

(1) For non isolated link, distance between the furthest devices: y 30 m.<br />

(2) For isolated link, tap isolation box TWD XCA ISO must be used.<br />

77