Functions<br />
<strong>Twido</strong> programmable <strong>controller</strong> 0<br />
Asynchronous serial links<br />
Modbus and character mode protocols<br />
Modbus serial link<br />
<strong>Twido</strong> (master)<br />
TeSys U<br />
TeSys U<br />
<strong>Twido</strong> slave<br />
Magelis XBT N<br />
The Modbus serial link meets the needs of<br />
master/slave architectures (it is nevertheless<br />
necessary to check that the Modbus services<br />
required for the application are implemented on the<br />
devices concerned).<br />
Modbus link<br />
Zelio Logic<br />
Advantys<br />
Advantys<br />
OTB OTB<br />
Preventa XPS MC<br />
ATV 31<br />
The bus consists of a master station and slave<br />
stations. Only the master station can initiate the<br />
exchange (direct communication between slave<br />
stations is not possible). Two exchange methods are<br />
possible:<br />
bQuestion/reply, questions from the master are<br />
addressed to a speci c slave. The master waits for<br />
the reply to be returned by the slave polled.<br />
b Distribution, the master distributes a message to all<br />
the slave stations on the bus. These stations execute<br />
the instruction without sending a reply.<br />
Modbus and character mode characteristics<br />
Protocol Modbus Character mode<br />
Structure Type Non isolated serial link (1)<br />
Access method Master/slave type –<br />
Physical interface RS 232, 3-wire RS 485, 3-wire RS 232, 3-wire RS 485, 3-wire<br />
Transmission Mode Asynchronous in basic band<br />
Frame RTU/ASCII, Half duplex Full duplex Half duplex<br />
Binary rate 0.3…38.4 Kbit/s (default 19.2 Kbit/s) 0.3…38.7 Kbit/s (default 19.2 Kbit/s)<br />
Format<br />
7 or 8 data bits, 1 or 2 stop bits<br />
Parity<br />
Without, even or odd<br />
Medium Shielded twisted pair Single or double Shielded twisted pair<br />
shielded twisted pair<br />
Configuration Number of devices 2 (point to point) 32 max per segment 2 (point to point) 32 max per segment<br />
Max. number of link addresses 244 248<br />
Max. length of bus (1) 15 m 10 m not isolated<br />
1000 m isolated (2)<br />
Max. length of a tap link – 10 m not isolated<br />
30 m isolated(2)<br />
Services Frame 250 bytes of data per request<br />
15 m 10 m not isolated<br />
1000 m isolated (2)<br />
– 10 m not isolated<br />
30 m isolated(2)<br />
Security, check parameter<br />
One CRC on each frame (RTU)<br />
One LRC on each frame (ASCII)<br />
One LRC on each frame (ASCII)<br />
Monitoring Diagnostic counters, event counters –<br />
Modbus functions<br />
Modbus functions available on <strong>Twido</strong> <strong>controller</strong> serial link Code Modbus slave (server) Modbus master (client)<br />
01 Read n internal bits %M Read output bits<br />
02 Read n internal bits %M Read input bits<br />
03 Read n internal words %MW Read words<br />
04 Read n internal words %MW Read input words<br />
05 Write 1 internal bit %M Write 1 bit or n bits<br />
06 Write 1 internal word %MW Write 1 word or n words<br />
15 Read n internal bits %M Write n output bits<br />
16 Write n internal words %MW Write n output words<br />
23 Read or write n internal words %MW, –<br />
only with 40 I/O compact base <strong>controller</strong><br />
TWD LCpp 40DRF<br />
43 Read device identi cation –<br />
(1) For non isolated link, distance between the furthest devices: y 30 m.<br />
(2) For isolated link, tap isolation box TWD XCA ISO must be used.<br />