Characteristics,<br />

references 4<br />

<strong>Twido</strong> programmable <strong>controller</strong> 4<br />

AS-Interface actuator/sensor bus<br />

AS-Interface master module<br />

Diagnostics<br />

The 30 pilot lights on the front panel of the module are used in conjunction with the<br />

two pushbuttons for diagnostics by the <strong>Twido</strong> <strong>controller</strong>.<br />

The display block on the front panel of master module TWD NOI 10M3 allows<br />

simpli ed local diagnostics to be performed by displaying the slaves present on the<br />

AS-Interface.<br />

Software set-up<br />

AS-Interface is con gured using <strong>Twido</strong>Suite (1) software.<br />

The services offered are based on the principle of simplicity:<br />

b Management of pro le tables, parameters and data by the master, in a way that is<br />

transparent to the user.<br />

b Topological addressing of I/O: each AS-Interface slave de ned has a topological<br />

address assigned to it, in a way that is transparent to the user.<br />

Each AS-Interface sensor/actuator is seen by the <strong>Twido</strong> programmable <strong>controller</strong> in<br />

the same way as any “In-rack” I/O.<br />

Characteristics<br />

Module type<br />

AS-Interface profile<br />

Type of addressing<br />

Product certifications AS-Interface n° 47801<br />

Degree of protection IP 20<br />

Temperature Operation °C 0…+ 55<br />

Storage °C - 25…+ 70<br />

As-Interface external power supply c V 29.5…31.6<br />

Internal current At c 5 V mA 80<br />

At c 24 V mA 0<br />

AS-Interface consumption at c 24 V mW 540<br />

Data exchange characteristics<br />

AS-Interface<br />

cycle time<br />

Max. number<br />

of modules<br />

Max. number<br />

of I/O<br />

Max. length of<br />

AS-Interface<br />

cable<br />

TWD NOI 10M3<br />

AS-Interface M3, V 2.11 (pro le S-7.4 not supported)<br />

Standard and extended<br />

With 1 to 19 slaves ms 3<br />

With 20 to 62 slaves ms 0.156 x (1 + N) where N = number of active slaves<br />

With 31 standard slaves<br />

ms 5<br />

or slaves in banks A and B<br />

With 62 slaves in banks A and B ms 10<br />

Analogue modules (1) 7<br />

Discrete modules (1) 62<br />

Standard slaves<br />

248 = 124 inputs + 124 outputs<br />

Slaves in banks A and B<br />

434 = 248 inputs + 186 outputs<br />

Without repeater or line extension m 100<br />

With line extension TCS ARR01M m 200<br />

With 2 repeaters ASI RPT01 m 300<br />

References<br />

Description<br />

AS-Interface<br />

master module for<br />

<strong>Twido</strong> base <strong>controller</strong><br />

- Compact<br />

TWD LCpp 24/40DRF<br />

- Modular<br />

TWD LMDA 20/40Dpp<br />

No. modules per<br />

base <strong>controller</strong><br />

AS-Interface<br />

profile<br />

Number of I/O<br />

(1)<br />

2 M3, V 2.11 62 discrete<br />

modules max.<br />

7 analogue<br />

modules max.<br />

Reference<br />

Weight<br />

kg<br />

TWD NOI 10M3 0.085<br />

TWD NOI 10M3<br />

Description Application Reference Weight<br />

kg<br />

Fixing kit<br />

Sold in lots of 5<br />

For plate or panel mounting of the module TWD XMT5 –<br />

(1) When analogue and discrete modules are connected simultaneously to a system, the<br />

analogue modules use addresses 1 to 31 in bank A. When an analogue module uses a certain<br />

address, the module addresses having the same number in bank B cannot be occupied by<br />

slaves in banks A/B.<br />