<strong>Profibus</strong> <strong>DP</strong> Mk2 <strong>Option</strong> <strong>Card</strong> <strong>Installation</strong> <strong>Manual</strong><br />

3.2 Inside a Q actuator<br />

The PFU is fitted in the option board position in this actuator. Only one option board may be fitted at<br />

any one time. The necessary internal components must also be present; in this case a potentiometer<br />

and auxiliary limit switches at end of travel must be fitted to the actuator.<br />

The illustration (Fig 5) shows the Q version of the circuit board. The links for the bias resistors are<br />

shown in the ‘not terminated’ position.<br />

EPROM<br />

LK1<br />

SK3<br />

SK9<br />

SK11<br />

SK10<br />

SK2<br />

Fig 5: The <strong>Profibus</strong> Mk2 card profiled for the Q actuator<br />

Digital Outputs from relay contacts are not supported from the Q actuator, nor is the ability to report<br />

the status of the remote control inputs as Digital Inputs. The following table shows the wiring<br />

harnesses that must be fitted and the function of each loom for the Q range actuator.<br />

PFU Socket<br />

Wiring Harness<br />

SK2<br />

24V power supply input from actuator<br />

SK3<br />

<strong>Profibus</strong> Fieldbus connection<br />

SK9<br />

Limit switches<br />

SK10 Analogue Input connection 1<br />

SK11<br />

Potentiometer<br />

Note: 1 - Only available on Single Channel module<br />

In a Q actuator there is a direct connection from PL2 on the Interface <strong>Card</strong> to SK5 of the actuator main<br />

board.<br />

To restore the card to its factory defaults and the associated default parameter settings, LK1 on the<br />

Interface card should be fitted and the power cycled (see Fig. 6).<br />

12 of 66 Publication S420E V3.0 Issue 01/05