20.09.2015 Views

Profibus Actuator Control Profibus DP Option Card Installation Manual

Profibus Actuator Control Profibus DP Option Card Installation Manual

Profibus Actuator Control Profibus DP Option Card Installation Manual

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Profibus</strong> <strong>DP</strong> Mk2 <strong>Option</strong> <strong>Card</strong> <strong>Installation</strong> <strong>Manual</strong><br />

Provided limited range positioning is not invoked the values 0% and<br />

100% written to the Position DV register produce a special case<br />

output where the command is revised so as to fully close the valve to<br />

its tight shut off position (0%) and fully open the valve (100%).<br />

Partial Stroke The actuator will move the valve to an intermediate position and back<br />

to the start position provided it is at the correct end of travel position<br />

when the command is issued. The end to start from and the amount of<br />

travel are selected during parameterisation.<br />

<br />

Multiport Position On multiport actuators the port to move to can be selected using this<br />

command. The actuator will move directly to the selected port. Valves<br />

with up to 10 ports can be controlled.<br />

Relay Output DO1 to DO4 These 4 commands are used to energise and deenergise<br />

the internal relays on the additional relay board in an IQ or<br />

IQT actuator. (These outputs are referred to as S5-S8 in the standard<br />

actuator documentation when there is no <strong>Profibus</strong> <strong>DP</strong> Module in the<br />

actuator.) The resulting outputs can be used for operating other<br />

equipment such as a pump or indication light. The IQ/IQT actuator is<br />

not able to control these relays directly from the main board when the<br />

PFU is fitted. They will maintain their last state if power is removed<br />

from the actuator. On restoration of power the relays will be reset to<br />

their de-energised condition and the coils will report ‘0’.<br />

<br />

<br />

<br />

Hard Wired Open and Close These commands operate the actuator in the same way<br />

as the open and close commands sent over the <strong>Profibus</strong> highway.<br />

Hard Wired Stop The hard wired stop input acts as a change of state input. If the<br />

actuator is moving, opening the Stop input will stop the actuator. If the<br />

Stop input is already open and a <strong>Profibus</strong> command is sent to the<br />

actuator, the <strong>Profibus</strong> command will be initiated. To stop the actuator<br />

the hard wired input must be closed and opened again.<br />

Hard Wired ESD (Network Disable) The hard wired ESD may be set to causes the<br />

actuator to drive to its Emergency position. Alternately the input can<br />

be used to disable <strong>Profibus</strong> network control. The function of the input<br />

is determined by the parameterisation set into the PFU.<br />

5.1.1 <strong>Control</strong>s Priority<br />

Since there are three potential sources for control inputs the actuator and <strong>Profibus</strong> <strong>DP</strong> Module (Mk2)<br />

assign a priority for those occasions when two or more commands are applied simultaneously.<br />

In addition, for the IQ and IQT actuator, the remote control hard wired inputs can be used as discrete<br />

input signals, to report the status of other devices or as control inputs. The associated Auxiliary Input<br />

Mask parameter must be set for the IQ or IQT to select the required function. In the case of the hard<br />

wired input for ESD this can be configured either as an ESD/DI-4 signal or as a ‘<strong>Profibus</strong> Command<br />

Inhibit’ to prevent network control signals from moving the actuator.<br />

30 of 66 Publication S420E V3.0 Issue 01/05

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!