20.09.2015 Views

Profibus Actuator Control Profibus DP Option Card Installation Manual

Profibus Actuator Control Profibus DP Option Card Installation Manual

Profibus Actuator Control Profibus DP Option Card Installation Manual

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Profibus</strong> <strong>DP</strong> Mk2 <strong>Option</strong> <strong>Card</strong> <strong>Installation</strong> <strong>Manual</strong><br />

Analogue Input The current value of the analogue input is reported as an Integer<br />

Value in the range 0 to 1000 (0 – 3E8 hex) representing the<br />

percentage value to 0.1% resolution.<br />

The input may be 0 to 5V or 0 to 20mA d.c. from an externally<br />

powered field transmitter (the actuator does not provide the power for<br />

the transmitter).<br />

The input must be calibrated during the set up of the PFU using the<br />

Analogue Input Max parameter. Apply a 100% signal and write a<br />

value to the parameter, the current value will then be reported as<br />

100%. The scaling is retained in EEPROM when the actuator power is<br />

removed.<br />

<br />

Multiport Position On multiport actuators the current number of the port selected is<br />

reported as an integer in the range 1 to 10 (1-A hex).<br />

5.4 Configuring the Registers to be Exchanged in Cyclic Communication<br />

In the start up routine for <strong>Profibus</strong> communication the card firstly enters parameterisation mode and<br />

adjusts the card parameters according to the GSD file settings. Next the card enters configuration<br />

mode where the configuration settings in the GSD file are used to determine the registers to be<br />

exchanged with the PLC during the normal cyclic messaging.<br />

The configuration stage allows for the tailoring of the registers to be exchanged to allow the system to<br />

be tuned to improve data throughput. If certain information or controls are not required by the PLC<br />

then they may be left out of data exchange by choosing the appropriate configuration.<br />

Both the PLC and the card must be aware of the configuration chosen for successful data exchange.<br />

The <strong>Profibus</strong> <strong>DP</strong> Module (Mk2) has 10 possible configurations as indicated in the table. The default<br />

value is Configuration 1. The PLC must send a Check Configuration message during start up to<br />

confirm the Configuration to be used.<br />

Configuration 1 2 3 4 5 6 7 8 9 10<br />

OUPUTS<br />

(16 Bits each)<br />

ACTCON <br />

POS_DV <br />

O_STAT <br />

PORTCM <br />

INPUTS<br />

(16 Bits each)<br />

IDATA1 & IDATA2 <br />

IDATA3 & IDATA4 <br />

TORQUE <br />

POSITN <br />

TEMPER <br />

ANALOG <br />

PORTST <br />

42 of 66 Publication S420E V3.0 Issue 01/05

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!