LK2<br />

SK1<br />

<strong>Profibus</strong> <strong>DP</strong> Mk2 <strong>Option</strong> <strong>Card</strong> <strong>Installation</strong> <strong>Manual</strong><br />

Data line 1B is positive with respect to data line 1A when the PFU is transmitting a ‘1’.<br />

Data line A is also called TxD/RxD-N<br />

Data line B is also called TxD/RxD-P<br />

If an analogue input is being used it is connected to the analogue input terminals. The <strong>Profibus</strong> card<br />

caters for both current and voltage analogue signals. There is no power supply on the card for the<br />

analogue transmitter and an external power supply must be used to power it.<br />

<br />

<br />

For voltage inputs connect I/P A to the positive signal and analogue Common to the<br />

negative signal from the transmitter<br />

For current inputs connect I/P A to I/P B (to insert the conditioning resistor). The current<br />

input positive is to I/P A and I/P B whilst the current input negative is connected to the<br />

analogue Common.<br />

Active termination resistors are included on the <strong>Profibus</strong> card. The jumper links LK1 and LK2 on the<br />

PNIC board are used to select the inclusion of these resistors.<br />

<br />

<br />

Fit LK1 and LK2 as shown to provide pull apart active termination to the network at this<br />

actuator and<br />

Link Terminals ‘Terminator’ and ‘<strong>Profibus</strong> A’ to add end of line termination<br />

EPROM<br />

LK3<br />

LK4<br />

LK2<br />

LK1<br />

Links shown<br />

in 'Terminate'<br />

position<br />

LK1<br />

SK3<br />

LK1<br />

SK5 SK7 SK10<br />

SK8<br />

SK2<br />

Fig 16: Single Highway Active Termination Links<br />

24 of 66 Publication S420E V3.0 Issue 01/05