20.09.2015 Views

Profibus Actuator Control Profibus DP Option Card Installation Manual

Profibus Actuator Control Profibus DP Option Card Installation Manual

Profibus Actuator Control Profibus DP Option Card Installation Manual

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Profibus</strong> <strong>DP</strong> Mk2 <strong>Option</strong> <strong>Card</strong> <strong>Installation</strong> <strong>Manual</strong><br />

6.5 Single Highway Dual Channel – FR Mode<br />

On either the Simple or RedCom dual channel card the mode for communications may be set to FR<br />

(Flying Redundancy) in some cases. This will require the card’s GSD file to be changed or the<br />

parameter value altered by a PDM or FDT utility.<br />

Redundancy SR is the default mode, it must be altered for FR mode<br />

In FR mode there is one highway and a single PLC can be used. The two channels on the card use<br />

addresses offset by 64. One channel is in Primary mode and uses the base address whilst the other is<br />

in Backup mode using the base address plus 64. As with SR mode, the card is waiting for a<br />

communication message on the channel that is in Primary mode and the two channels will switch their<br />

mode whilst searching for comms. There is no definition between Channel 1 and Channel 2 to<br />

determine which is in Primary mode. The two channels will both try to adopt Primary mode. The<br />

difference here is that the PLC can communicate with the backup using a different address.<br />

When using either type of dual channel card in FR mode the following must be set up:<br />

Address The two channels have address offset by 64. Setting the base<br />

address will set the offset address. With IQ and IQT actuators the<br />

address can be set using the IrDA communication link directly with the<br />

actuator and the IQ setting tool. For all actuator variants the address<br />

can be set over the highway using a Class 2 master.<br />

Baud Rate This is selected by the PLC, both channels adopt the same baud rate<br />

Slave Configuration One of the 10 configurations for the slave must be chosen. Both<br />

channels will use the same configuration setting.<br />

Configuration can only be carried out on the Primary channel.<br />

<br />

Basic Parameterisation The basic parameters such as deadband and motion inhibit<br />

time can be set using either the GSD file or a suitable PDM or FDT<br />

utility. The default settings will be suitable for most systems. Both<br />

channels will adopt the same settings.<br />

Parameterisation can only be carried out on the Primary channel.<br />

IDATA4 Bit 5 indicates the channel status and will show if the channel<br />

in communication is the Primary or Backup.<br />

FR<br />

Master PLC<br />

Standby PLC<br />

Highway 1<br />

Primary Backup<br />

address # =n address # = 64+n<br />

<strong>Profibus</strong> <strong>Card</strong><br />

Fig 25: Flying Redundancy – One highway redundancy<br />

46 of 66 Publication S420E V3.0 Issue 01/05

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!