3.8 CONNECTING THE <strong>OUTPUT</strong> CHANNELS<br />
The two 4–20 mA DC output channels are capable of driving into a 600 _ load. Refer to Figure 3.8.<br />
3.9 CONNECTING THE ALARMS<br />
Figure 3.8 Connections for Transmitter Output Channels.<br />
The alarm relay functions are described in detail in Sections 4.2 and 4.3. Each relay, except for the horn relay, has<br />
normally closed contacts. The contacts will open in alarm condition. The horn relay has normally open contacts.<br />
All systems should have the alarm relay RL5 connected to Terminals 26 and 27, and the probe low temperature<br />
relay RL3 connected. The probe calibration and horn relays are optional. Alarm wiring should be shielded.<br />
3.10 CONNECTING THE HORN RELAY<br />
The horn relay operates as a true alarm system and can be connected directly to a horn. The horn relay is latching<br />
and can be reset by pressing the alarm button. Refer to Figure 3.9.<br />
3.6 NOVATECH <strong>OXYGEN</strong> ANALYSER