PID control Functions<br />

Buffer Memory<br />

Address (decimal)<br />

Name Description<br />

Real value/<br />

Set value<br />

0 to 9 Measured values<br />

Scaled values from the analog<br />

inputs<br />

Real values<br />

10 to 19 <strong>Control</strong> output value ON ratio of the outputs [%] Real values<br />

20 to 21 Output states<br />

Shows whether the outputs are ON<br />

or OFF<br />

Real values<br />

27 Status flags of the <strong>RE10TC</strong><br />

Indication whether setpoints for<br />

stand-by mode are active or not<br />

Real values<br />

120 to 129 Set values Set values for the temperatures Set values<br />

130 to 139 Set values for stand-by mode Set values for the stand-by mode Set values<br />

180 to 189<br />

190 to 199<br />

Proportional band XP<br />

(heating)<br />

Proportional band XP<br />

(cooling)<br />

Settings for the temperature controllers<br />

200 to 209 Integral time TI<br />

210 to 219 Derivative time TD<br />

220 to 229 Shortest ON time (Heating) Setting of the shortest ON time for<br />

230 to 239 Shortest ON time (Cooling) the outputs<br />

290 to 292 Leading values<br />

These settings are valid until switching<br />

(BFM #293).<br />

Set values<br />

Set values<br />

Set values<br />

293 Value for switching<br />

Switching between master and regular<br />

settings<br />

Set value<br />

305 to 314 Cooling constant Constant for water cooling Set values<br />

315 to 324 Starting point for cooling constant<br />

Sets the actual value from which on<br />

the cooling constant will be valid<br />

Set values<br />

340 <strong>Control</strong> flags from CPU of PLC Activation of setpoints, settings etc. Set value<br />

341 <strong>Control</strong>ler ON/OFF Selection of temperature controllers Set value<br />

Tab. 2-1: Buffer memory areas for temperature control<br />