Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
428<br />
ABB i-bus ® KNX<br />
Product Article-No. Order-No. Pack/Qty<br />
KNX universal interface 1 )<br />
2gang<br />
The universal interface has 2 channels. These channels<br />
can be parameterised as an input or output using ETS.<br />
Conventional push-switches, auxiliary contacts, luminous<br />
diodes, and the ER/U electrical relay can be connected to<br />
the connecting lines. These lines can be extended up to<br />
10 m.<br />
The contact scanning voltage and the feed voltage for the<br />
LEDs are provided by the device, and the series resistors<br />
for the LEDs are integrated.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Inputs: 2<br />
Polling voltage: 20 V<br />
Outputs: 2x electronic output, potential-bound<br />
Supply voltage: 5 V<br />
Rated current: 2 mA<br />
Protection class (Device): IP 20<br />
Temperature range (Device): -5 °C to 45 °C<br />
Dimensions: (L x W x D): 39 mm x 40 mm x 12 mm<br />
US/U 2.2 GHQ6310074R0111<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
KNX universal interface 1 )<br />
4gang<br />
The universal interface has 4 channels. These channels<br />
can be parameterised as an input or output using ETS.<br />
Conventional push-switches, auxiliary contacts, luminous<br />
diodes, and the ER/U electrical relay can be connected to<br />
the connecting lines. These lines can be extended up to<br />
10 m.<br />
The contact scanning voltage and the feed voltage for the<br />
LEDs are provided by the device, and the series resistors<br />
for the LEDs are integrated.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Inputs: 4<br />
Polling voltage: 20 V<br />
Outputs: 2x electronic output, potential-bound<br />
Rated current: 2 mA<br />
Protection class (Device): IP 20<br />
Temperature range (Device): -5 °C to 45 °C<br />
Dimensions: (L x W x D): 39 mm x 40 mm x 12 mm<br />
US/U 4.2 GHQ6310070R0111<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
Technical information<br />
www.BUSCH-JAEGER-catalogue.com<br />
Product Article-No. Order-No. Pack/Qty<br />
Universal interface<br />
12gang<br />
The device has 12 channels that can be parameterised as<br />
individually as inputs or outputs through selection in the<br />
application program.<br />
Convention push-switches, fl oating contacts, or luminous<br />
diodes can be connected.<br />
The contact scanning voltage of the contacts and the feed<br />
voltage for the LEDs are provided by the device.<br />
Series resistors for external luminous diodes are installed<br />
in the device.<br />
The universal interface is installed into a device connecting<br />
socket, 60 mm, in a fl ush-mounted manner.<br />
The following functions can be set according to input:-<br />
Any reaction to an edge at the output- Sending of switch/<br />
dimmer commands- Operation of dimmable lighting via a<br />
single push-switch- Operation of blinds via a single pushswitch-<br />
Control and saving of light scenes- Sending any<br />
values to data types- Switching of several loads in fi xed<br />
switching sequences- Generation of a PWM signal for a<br />
heating control system- Switching and fl ashing of LEDs.<br />
Channels: 12, can be parameterised individually as input<br />
or output; output scanning voltage: 20 V pulses; input current:<br />
0.5 mA; output voltage of output: 3.3 V DC; output<br />
current: max. 2 mA, limited via series resistor; connection<br />
of inputs/outputs: 3x6 lines, approx. 30 cm long, pluggable,<br />
extendable to a maximum of 10 m; bus connection:<br />
bus connecting terminal; dimensions (dia. x H): 54 x 19<br />
mm; degree of protection: IP 20, EN 60529.<br />
US/U 12.2 2CDG110065R0011<br />
Heating actuator 1 )<br />
1-gang actuator<br />
1 electronic output (noiseless)<br />
For connecting the thermoelectric valve drives TSA/K<br />
230.1 or TSA/K 24.1<br />
Per channel a maximum of 5 positioners can be connected<br />
in parallel<br />
2 inputs for potential free contacts<br />
Connecting cables max. 10 m<br />
The bus connection is effected via the enclosed bus<br />
terminal.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Rated voltage: 230 V~, +10 % / -10 %<br />
Output voltage: 24 V~<br />
Rated frequency: 50 Hz<br />
Outputs: 1x electronic output, potential free<br />
Suitable for: AC1<br />
Rated current: 1 A, cos 1<br />
Protection class (Device): IP 20<br />
Temperature range (Device): -25 °C to 60 °C<br />
Dimensions: (L x W x D): 53 mm x 52 mm x 24 mm<br />
6164 U-500 6151-0-0168 1/10<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.