ABB i-bus ® KNX<br />
Product Article-No. Order-No. Pack/Qty<br />
DCF time transmitter 1 ) 2 ) 3 )<br />
2-channel<br />
For transmitting time and date to the KNX bus.<br />
For synchronising other bus devices.<br />
With automatic changeover between summer/winter<br />
time.<br />
Can be operated with or without DCF aerial.<br />
Power pack for DCF reception is integrated.<br />
Radio-controlled in conjunction with supplementary aerial<br />
FA/A 2.1.<br />
Power reserve: approx. 10 years<br />
The bus connection is effected via the enclosed bus<br />
terminal.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Protection class (Device): IP 20<br />
Temperature range (Device): -10 °C to 50 °C<br />
Dimensions: (L x W x D): 86 mm x 35 mm x 65.5 mm<br />
module width: 2 MW<br />
6145/10 6140-0-0027 1<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
2) 1 MW 18 mm.<br />
3) Documentation only available in German.<br />
Light sensor 1 ) 2 )<br />
3-channel<br />
Controls the lighting dependent on daylight using ABB<br />
i-bus ®<br />
KN X.<br />
Applications can be set as twilight switches (1 to 100<br />
lx) or light value switches (100 to 20 000 lx) during the<br />
parameterisation of the device.<br />
The light sensor is included in delivery.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Inputs: 1<br />
Brightness limit value: 1 Lux - 20000 Lux<br />
Protection class (Device): IP 20<br />
Protection class (Sensor): IP 54<br />
Temperature range (Device): -5 °C to 45 °C<br />
Temperature range (Sensor): -40 °C to 70 °C<br />
Dimensions: (L x W x D): 45 mm x 36 mm x 65.5 mm<br />
module width: 2 MW<br />
HS/S 3.1 GHQ6050063R0001<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
2) 1 MW 18 mm.<br />
Brightness, temperature switch 1 ) 2 )<br />
3gang<br />
For detecting and controlling the brightness and temperature.<br />
Threshold switch for controlling switching, dimming and<br />
blind actuators depending on the ambient brightness and/<br />
or temperature.<br />
Ability to disable one or more threshold switches.<br />
The bus connection is made via a bus terminal.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Inputs: 2<br />
Brightness limit value: 1 Lux - 100000 Lux<br />
Protection class (Device): IP 54<br />
Temperature range (Device): -25 °C to 55 °C<br />
Dimensions: (L x W x D): 110 mm x 72 mm x 54 mm<br />
6146/10 6146-0-0022 1<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
2) Documentation only available in German.<br />
Technical information<br />
www.BUSCH-JAEGER-catalogue.com<br />
Product Article-No. Order-No. Pack/Qty<br />
Weather station 1 ) 2 )<br />
4gang<br />
The WS/S 4.1 weather station enables the recording and<br />
processing of four independent, analogue input signals<br />
according to DIN IEC 60381 (0-1 V, 0-5 V, 0-10 V, 1-10 V,<br />
0-20 mA, 4-20 mA, 0-1000 Ohm, PT 100 in 2-conductor<br />
technology and fl oating contact).<br />
A power pack with 24 V DC voltage has been integrated to<br />
supply the sensors.<br />
The device can alternatively be operated with an operating<br />
voltage of 115 to 230 V AC, 50/60 Hz.<br />
A maximum of 300 mA is available across the entire voltage<br />
range.<br />
The application software is suited for the recording of<br />
weather data.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Rated voltage: 24 V~, +15 % / -15 %<br />
Secondary: 24 V<br />
Inputs: 4<br />
Polling voltage: , Input resistance approx. 18 kOhm<br />
Outputs: 2<br />
Rated current: 100 mA<br />
Output voltage: 24 V<br />
Protection class (Device): IP 20<br />
Temperature range (Device): -5 °C to 45 °C<br />
Dimensions: (L x W x D): 90 mm x 72 mm x 58 mm<br />
Installation depth: 68 mm<br />
module width: 4 MW<br />
WS/S 4.1 2CDG110032R0011<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
2) 1 MW 18 mm.<br />
Weather unit 1 ) 2 )<br />
The WZ/S 1.1 detects and processes weather date it<br />
receives from the weather sensor. The weather sensor<br />
supplies data on twilight, brightness in three directions,<br />
rain, temperature, information on day/night, wind speeds,<br />
and time and date.<br />
The WZ/S 1.1 weather station is adapted to the WES/A<br />
weather sensor.<br />
The weather sensor is directly supplied with power via the<br />
integrated power pack.<br />
The device can alternatively be operated with an operating<br />
voltage of 115 to 230 V AC, 50/60 Hz.<br />
Connections:<br />
KNX-line: Bus terminal<br />
Rated voltage: 230 V~, +10 % / -15 %<br />
Rated frequency: 50 Hz/60 Hz<br />
Inputs: 1<br />
Protection class (Device): IP 20<br />
Temperature range (Device): -5 °C to 45 °C<br />
Dimensions: (L x W x D): 90 mm x 72 mm x 58 mm<br />
Installation depth: 68 mm<br />
module width: 4 MW<br />
WZ/S 1.1 2CDG110034R0011<br />
1) As required, you can fi nd the programmable functions in the current application description, which<br />
you can download in the Support Centre on our Internet page.<br />
2) 1 MW 18 mm.<br />
Weather sensor<br />
The WES/A 1.1 records data on twilight, brightness in<br />
three directions, rain (upper sensor surface permanently<br />
heated, lower sensor surface for temperatures < 10° or<br />
precipitation), temperature, information on day/night, wind<br />
speeds, and time and date (DCF radio receiver).<br />
An additional heating transformer is not required.<br />
The WES/A 1.1 weather unit is adapted to the WZ/S<br />
weather sensor.<br />
Protection class (Device): IP 65<br />
Temperature range (Device): -30 °C to 70 °C<br />
Dimensions: (L x W x D): 80 mm x 67 mm x 125 mm<br />
WES/A 1.1 2CDG120003R0011