2-8 <strong>Earthquake</strong> <strong>Protection</strong><br />
Page 36 <strong>FM</strong> <strong>Global</strong> Property Loss Prevention Data Sheets<br />
E. Provide a flexible coupling within 2 ft (0.6 m) above the initial in-rack sprinkler pipe drop attachment<br />
to the rack (see Fig. 20).<br />
F. Provide flexible coupling(s) on the horizontal portion of in-rack sprinkler piping within 2 ft (0.6 m) of<br />
the connections to vertical pipe drops (see Fig. 20).<br />
G. When pipe drops supplying in-rack sprinklers are connected to overhead horizontal piping via an<br />
armover, no flexible couplings are needed on the armover. However, provide a hanger of the type that<br />
will resist vertical upward movement per Section 2.2.1.8.1(B) and Figure 20.<br />
Fig. 19. Arrangement of combination risers <strong>for</strong> ceiling sprinklers and in-rack sprinklers/hose stations<br />
2.2.1.4.6 For drops to below suspended ceilings, mezzanines, walkways, etc. that supply more than one<br />
sprinkler (see Fig. 21), provide flexibility per the following guidelines.<br />
A. Provide a flexible coupling within 2 ft (0.6 m) of the connection to overhead piping or armovers <strong>for</strong><br />
pipe drops that exceed 2 ft (0.6 m) in length.<br />
B. Provide flexible coupling(s) on the horizontal portion within 2 ft (0.6 m) of any tee or elbow connecting<br />
pipe drops to sprinkler piping beneath ceilings, mezzanines, walkways, etc.<br />
©2010 Factory Mutual Insurance Company. All rights reserved.