22.01.2013 Views

DS 2-8 Earthquake Protection for Water-Based Fire ... - FM Global

DS 2-8 Earthquake Protection for Water-Based Fire ... - FM Global

DS 2-8 Earthquake Protection for Water-Based Fire ... - FM Global

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2-8 <strong>Earthquake</strong> <strong>Protection</strong><br />

Page 44 <strong>FM</strong> <strong>Global</strong> Property Loss Prevention Data Sheets<br />

• Schedule of sway bracing type, size, and design criteria (length, angle from vertical, and load<br />

capacities), and<br />

• Details of attachment to the structure and to the piping, including verification of structural capacity<br />

to withstand seismic load, details of sizing and load capacities of fasteners, and verification of load<br />

capabilities of anchors not covered in this data sheet.<br />

B. Location of flexible couplings and seismic separation assemblies.<br />

C. Location of clearances around piping <strong>for</strong> seismic purposes.<br />

D. Anchorage or seismic design details <strong>for</strong> storage racks that have in-rack sprinklers.<br />

E. Anchorage or seismic design details <strong>for</strong> suspended ceilings beneath which sprinklers are installed.<br />

F. For fire pump installations, all seismic design details as outlined in Section 2.2.5.<br />

G. For water storage tanks or reservoirs, all seismic design details as outlined in Section 2.2.6.<br />

2.3 Using Other Codes and Standards<br />

Other codes and standards listed below, when used with the noted limitations, exceptions, and additions,<br />

provide earthquake protection of fire protection systems similar to that recommended in this data sheet.<br />

2.3.1 National <strong>Fire</strong> <strong>Protection</strong> Association (NFPA) Standards<br />

2.3.1.1 NFPA 13, 2007 Edition<br />

NFPA 13, Standard <strong>for</strong> the Installation of Sprinkler Systems, 2007 Edition, Section 9.3, “<strong>Protection</strong> of Piping<br />

Against Damage Where Subject to <strong>Earthquake</strong>s” (and its associated appendix), is similar in most respects<br />

to this data sheet’s recommendations <strong>for</strong> the sprinkler system itself. However, NFPA 13 does not address<br />

some items (such as earthquake protection of water supplies and pumps, or anchorage of equipment) that<br />

can impact sprinkler systems.<br />

NFPA 13 (2007), Section 9.3, can be used with the changes noted below to provide earthquake protection<br />

similar to that recommended in this data sheet.<br />

2.3.1.1.1 Bracing of Piping: In addition to the NFPA 13 (2007) requirements, adhere to the recommendations<br />

from Section 2.2 of this data sheet <strong>for</strong> the following items related to bracing of piping.<br />

A. In multistory buildings, lay out intermediate 4-way bracing on risers so that bracing is provided at each<br />

floor having a supply main.<br />

B. Brace horizontal manifolds at the base of risers per Section 2.2.1.1.2(C) of this data sheet.<br />

C. Provide 4-way bracing at both the top and bottom of vertical feedmains and crossmains 6 ft (1.8 m)<br />

or longer per Section 2.2.1.1.3(A) of this data sheet.<br />

D. Do not omit lateral bracing on feedmains and crossmains (regardless of size) nor on branch lines 4<br />

in. (100 mm) and larger where the pipe is supported by short rod hangers (i.e., do not apply NFPA 13<br />

Section 9.3.5.3.8 to these pipes).<br />

E. Do not use wraparound U-hangers and U-hangers that hold the pipe tight against the underside of a<br />

structural member as lateral braces on feedmains and crossmains, regardless of size (i.e., do not apply<br />

NFPA 13 Section 9.3.5.3.9 to feedmains and crossmains). U-bolts, however, may be used as lateral<br />

braces per Section 2.2.1.3.2 of this data sheet.<br />

F. Provide lateral and longitudinal braces at changes of direction <strong>for</strong> horizontal feedmains and crossmains<br />

per Section 2.2.1.1.4(A) of this data sheet.<br />

G. Provide longitudinal bracing on branch lines 2- 1 ⁄ 2 in. (65 mm) and larger per Section 2.2.1.1.5(B) of<br />

this data sheet. Branch line longitudinal bracing should not be used to brace the crossmain.<br />

H. Limit the l/r ratio <strong>for</strong> braces used in compression to 200 or less (modification of NFPA 13 Section<br />

9.3.5.8.2). Limit the l/r ratio <strong>for</strong> braces used in tension to 300 or less. Do not use cable or wire bracing<br />

(i.e., do not apply NFPA 13 Section 9.3.5.2.2).<br />

©2010 Factory Mutual Insurance Company. All rights reserved.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!