<strong>Earthquake</strong> <strong>Protection</strong> 2-8<br />
<strong>FM</strong> <strong>Global</strong> Property Loss Prevention Data Sheets Page 37<br />
Fig. 20. Arrangements <strong>for</strong> piping feeding in-rack sprinklers.<br />
C. Provide a flexible coupling within 2 ft (0.6 m) above and/or below any intermediate points of lateral<br />
restraint when needed to accommodate differential movement.<br />
D. When pipe drops are connected to overhead horizontal piping via an armover, no flexible couplings<br />
are needed on the armover itself. See Section 2.2.1.8.1(B) <strong>for</strong> guidance on hangers supporting armovers.<br />