GB<br />

4<br />

Alarms<br />

displayed<br />

Meaning<br />

Condition for the<br />

alarm signalling<br />

Condition for the alarm<br />

interruption<br />

Check and<br />

connections<br />

L02<br />

Incompatibility between<br />

the MI and ME range<br />

Incompatible ME model<br />

with MI<br />

Interruption when restarted<br />

1. Check the EEPROM of<br />

MI<br />

2. Check the external<br />

electronic board of MI<br />

L04<br />

Defect in the definition of<br />

the parameters<br />

ME address duplicated<br />

(addressing system)<br />

Interruption when restarted<br />

1. Check the address of ME<br />

2. Check the<br />

communication cabling<br />

bus<br />

L07<br />

Defect in the definition of<br />

the parameters<br />

On the internal unit there<br />

is an error in the cabling.<br />

Interruption of the alarm for<br />

interruption to the power<br />

supply + restoration of the<br />

power supply<br />

1. Check the address of MI<br />

2. Check the<br />

communication cabling<br />

bus<br />

L10<br />

Defect in the definition of<br />

the parameters<br />

The power parameter is<br />

absent in the ME<br />

Interruption of the alarm for<br />

interruption to the power supply<br />

+ restoration of the power supply<br />

EEPROM of ME check<br />

L13<br />

Incompatibility between<br />

the MI and ME range<br />

MI model is incompatible<br />

with ME<br />

Interruption of the alarm for<br />

interruption to the power<br />

supply + restoration of the<br />

power supply<br />

1. Check the EEPROM of<br />

MI<br />

2. Check the external<br />

electronic board<br />

E06<br />

ME detects an anomalous<br />

signal from the MI<br />

Defect in the reception of<br />

the information<br />

(unsuccessful check for<br />

the number of MI)<br />

Automatic interruption of<br />

the alarm<br />

1. Check ME<br />

2. Check the<br />

communication<br />

cabling bus<br />

E07<br />

Missing communication<br />

from ME towards MI<br />

Defect in communication<br />

upon start-up<br />

Automatic interruption of<br />

the alarm<br />

1. Check the communication<br />

cabling bus<br />

2. Check the external<br />

electronic board<br />

E14<br />

Defect in the definition of<br />

the parameters<br />

Duplication of the main<br />

unit in a multisimultaneous<br />

system<br />

(detection of ME)<br />

Interruption of the alarm for<br />

interruption to the power<br />

supply + restoration of the<br />

power supply<br />

1. Check the communication<br />

cabling bus<br />

2. Check the MI<br />

combination<br />

E15<br />

Defect during automatic<br />

addressing<br />

MI power too low<br />

Interruption of the alarm for<br />

interruption to the power<br />

supply + restoration of the<br />

power supply<br />

1. Check the communication<br />

cabling bus<br />

2. Check the external<br />

electronic board<br />

E16<br />

Defect during automatic<br />

addressing<br />

MI power too high<br />

Interruption of the alarm for<br />

interruption to the power<br />

supply + restoration of the<br />

power supply<br />

1. Check the communication<br />

cabling bus<br />

2. Check the external<br />

electronic board<br />

E20<br />

Interrupted<br />

addressing<br />

automatic<br />

ME cannot receive any<br />

signal arriving from MI<br />

Interruption of the alarm for<br />

interruption to the power<br />

supply + restoration of the<br />

power supply<br />

1. Check the communication<br />

cabling bus<br />

2. Check the external<br />

electronic board<br />

E31<br />

Communication defect<br />

within the unit<br />

Impossible<br />

to<br />

communicate with the<br />

MDC for 3 or more minutes<br />

Automatic interruption of<br />

the alarm<br />

Check the external<br />

electronic board<br />

H01<br />

Overcurrent<br />

The Inverter stops when<br />

the alarm intervenes<br />

Interruption when restarted<br />

1. Thermodynamic defect<br />

Operation in overload<br />

2. Tightening defect<br />

between the HIC board<br />

and the cooling radiator<br />

3. Cooling defect of the<br />

radiant plate<br />

4. Check external board<br />

cabling<br />

<strong>SHERPA</strong><br />

57