SHERPA 275678A_1_18.pmd - Olimpia Splendid
SHERPA 275678A_1_18.pmd - Olimpia Splendid
SHERPA 275678A_1_18.pmd - Olimpia Splendid
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
GB<br />
4<br />
Alarms<br />
displayed<br />
Meaning<br />
Condition for the<br />
alarm signalling<br />
Condition for the alarm<br />
interruption<br />
Check and<br />
connections<br />
L02<br />
Incompatibility between<br />
the MI and ME range<br />
Incompatible ME model<br />
with MI<br />
Interruption when restarted<br />
1. Check the EEPROM of<br />
MI<br />
2. Check the external<br />
electronic board of MI<br />
L04<br />
Defect in the definition of<br />
the parameters<br />
ME address duplicated<br />
(addressing system)<br />
Interruption when restarted<br />
1. Check the address of ME<br />
2. Check the<br />
communication cabling<br />
bus<br />
L07<br />
Defect in the definition of<br />
the parameters<br />
On the internal unit there<br />
is an error in the cabling.<br />
Interruption of the alarm for<br />
interruption to the power<br />
supply + restoration of the<br />
power supply<br />
1. Check the address of MI<br />
2. Check the<br />
communication cabling<br />
bus<br />
L10<br />
Defect in the definition of<br />
the parameters<br />
The power parameter is<br />
absent in the ME<br />
Interruption of the alarm for<br />
interruption to the power supply<br />
+ restoration of the power supply<br />
EEPROM of ME check<br />
L13<br />
Incompatibility between<br />
the MI and ME range<br />
MI model is incompatible<br />
with ME<br />
Interruption of the alarm for<br />
interruption to the power<br />
supply + restoration of the<br />
power supply<br />
1. Check the EEPROM of<br />
MI<br />
2. Check the external<br />
electronic board<br />
E06<br />
ME detects an anomalous<br />
signal from the MI<br />
Defect in the reception of<br />
the information<br />
(unsuccessful check for<br />
the number of MI)<br />
Automatic interruption of<br />
the alarm<br />
1. Check ME<br />
2. Check the<br />
communication<br />
cabling bus<br />
E07<br />
Missing communication<br />
from ME towards MI<br />
Defect in communication<br />
upon start-up<br />
Automatic interruption of<br />
the alarm<br />
1. Check the communication<br />
cabling bus<br />
2. Check the external<br />
electronic board<br />
E14<br />
Defect in the definition of<br />
the parameters<br />
Duplication of the main<br />
unit in a multisimultaneous<br />
system<br />
(detection of ME)<br />
Interruption of the alarm for<br />
interruption to the power<br />
supply + restoration of the<br />
power supply<br />
1. Check the communication<br />
cabling bus<br />
2. Check the MI<br />
combination<br />
E15<br />
Defect during automatic<br />
addressing<br />
MI power too low<br />
Interruption of the alarm for<br />
interruption to the power<br />
supply + restoration of the<br />
power supply<br />
1. Check the communication<br />
cabling bus<br />
2. Check the external<br />
electronic board<br />
E16<br />
Defect during automatic<br />
addressing<br />
MI power too high<br />
Interruption of the alarm for<br />
interruption to the power<br />
supply + restoration of the<br />
power supply<br />
1. Check the communication<br />
cabling bus<br />
2. Check the external<br />
electronic board<br />
E20<br />
Interrupted<br />
addressing<br />
automatic<br />
ME cannot receive any<br />
signal arriving from MI<br />
Interruption of the alarm for<br />
interruption to the power<br />
supply + restoration of the<br />
power supply<br />
1. Check the communication<br />
cabling bus<br />
2. Check the external<br />
electronic board<br />
E31<br />
Communication defect<br />
within the unit<br />
Impossible<br />
to<br />
communicate with the<br />
MDC for 3 or more minutes<br />
Automatic interruption of<br />
the alarm<br />
Check the external<br />
electronic board<br />
H01<br />
Overcurrent<br />
The Inverter stops when<br />
the alarm intervenes<br />
Interruption when restarted<br />
1. Thermodynamic defect<br />
Operation in overload<br />
2. Tightening defect<br />
between the HIC board<br />
and the cooling radiator<br />
3. Cooling defect of the<br />
radiant plate<br />
4. Check external board<br />
cabling<br />
<strong>SHERPA</strong><br />
57