SIMOTICS XP 1MB1, 1MB5 explosion-protected motors<br />

Orientation<br />

■ Overview<br />

Temperature classes and groups<br />

Combustible gases and vapors are divided into temperature<br />

classes according to their ignitability and into groups according<br />

to their spark ignition capacity. The marking of a three-phase<br />

motor with the codes for the type of protection, group and temperature<br />

class specifies that it can be used without danger in<br />

hazardous areas depending on the zone classification. The numerical<br />

sequence of the codes for the group and temperature<br />

class has been selected so that motors that satisfy the requirements<br />

for a certain group and temperature class also satisfy the<br />

requirements for lower groups and classes.<br />

Temperature classes<br />

Temperature class<br />

of electrical<br />

equipment<br />

Maximum surface<br />

temperature of electrical<br />

equipment<br />

T1 450 °C > 450 °C<br />

T2 300 °C > 300 °C<br />

T3 200 °C > 200 °C<br />

T4 135 °C > 135 °C<br />

T5 100 °C > 100 °C<br />

T6 85 °C > 85 °C<br />

Examples of the assignment of combustible gases and vapors<br />

Group Temperature classes<br />

T1 T2 T3 T4 T5 T6<br />

Material<br />

designation<br />

Ignition<br />

temperature<br />

Material<br />

designation<br />

Ignition<br />

temperature<br />

Material<br />

designation<br />

Ignition<br />

temperature<br />

Material<br />

designation<br />

Ignition<br />

temperature<br />

Material<br />

designation<br />

Ignition<br />

temperature<br />

Ignition temperature of<br />

gases or vapors<br />

Material<br />

designation<br />

Ethyl acetate 460<br />

n-Butyl<br />

alchohol<br />

340 Mineral<br />

spirits<br />

2)<br />

Ignition<br />

temperature<br />

°C °C °C °C °C °C<br />

IIA 1) Acetone 540 i-Amyl 380 Naphthas Acetaldehyde<br />

140<br />

acetate<br />

Ethane 515 n-Butane 365 Petrol fuels 2)<br />

Ethyl chloride 510 Cyclohexanone<br />

Ammonia 630 1,2-Dichloroethane<br />

430 Diesel fuels<br />

440 Heating oils<br />

2)<br />

2)<br />

5<br />

Benzene 555 Acetic anhydride<br />

330 n-Hexane 240<br />

Acetic acid 485<br />

Carbon 605<br />

monoxide<br />

Methane 595<br />

Methanol 455<br />

Methyl 625<br />

chloride<br />

Naphtalene 520<br />

Phenol 595<br />

Propane 470<br />

Toluene 535<br />

IIB 1) Coal gas 560 Ethanol 425 Hydrogen 270 Ethyl ether 180<br />

(town gas)<br />

Ethylene 425<br />

sulfide<br />

Ethylene 440<br />

oxide<br />

IIC 1) Hydrogen 560 Acetylene 305 Carbon<br />

disulfide<br />

Explosion Protection Directive 2014/34/EU<br />

Explosion protection has been fully harmonized by Directive<br />

2014/34/EU in Germany and in the other member states of the<br />

European Union. The requirements of the new law came into<br />

force on April 20, 2016. Since then only those devices and protection<br />

systems that comply with Directive 2014/34/EU are permitted<br />

to be placed on the market.<br />

Directive 2014/34/EU and Directive 1999/92/EC specify that only<br />

specific electrical equipment and devices are permitted to be<br />

used in the zones. The devices are assigned to equipment<br />

groups and categories.<br />

Use of electrical equipment in accordance with EN 60079-14<br />

Electrical equipment used in potentially explosive workshops<br />

and storage areas must comply with EN 60079-14/ VDE 0165-1<br />

"Explosive atmospheres - Part 14: Electrical installations design,<br />

selection and erection". All other general regulations issued by<br />

the responsible supervisory authorities and the Employer's<br />

Liability Insurance Association or any specifically issued for<br />

individual case are also applicable. A plant or system subject to<br />

inspection is not permitted to be commissioned initially or following<br />

a significant modification until the plant or system has been<br />

inspected by an approved inspection agency for correctness of<br />

assembly, installation, site conditions and safe operation, taking<br />

into account the intended mode of operation. Devices compliant<br />

with Directive 2014/34/EU are permitted to be commissioned in<br />

accordance with the responsible supervisory authority.<br />

(cf. German Health and Safety at Work Regulations (BetrSichV),<br />

section 3, § 14)<br />

95<br />

1)<br />

Subgroups IIA, IIB and IIC must be specified for the types of protection<br />

Ex db, Ex eb and Ex ec described in this list in accordance with EN 60079-0.<br />

2)<br />

The minimum ignition temperature depends on the composition and lies<br />

between 220 to 300 °C, over 300 °C in special cases.<br />

5/4 Siemens D 81.1 · <strong>06</strong>/<strong>2020</strong>