© Siemens <strong>2020</strong><br />

SIMOTICS XP 1MB1, 1MB5 explosion-protected motors<br />

Article No. supplements and special versions · Motor protection<br />

Cast-iron series 1MB1543, 1MB5543 Basic Line and 1MB1643, 1MB5643 Performance Line<br />

■ Selection and ordering data<br />

Motor protection Article No. supplement Frame size Motor version<br />

<br />

✓<br />

1MB1543 - . . . . . - . . ■ .<br />

1MB1643 - . . . . . - . . ■ .<br />

1MB5543 - . . . . . - . . ■ .<br />

1MB5643 - . . . . . - . . ■ .<br />

Standard version<br />

With additional charge<br />

Motor<br />

protection<br />

code letter<br />

15th position<br />

of the<br />

Article No.<br />

Additional<br />

identification<br />

code with<br />

order code<br />

and plain text,<br />

if required<br />

Order code<br />

71 80 90 100 112 132 160 180 200 225 250 280 315<br />

1MB1543 Basic Line IEC Ex eb (Zone 1) IE3<br />

1MB1643 Performance Line<br />

1MB5543 Basic Line<br />

1MB5643 Performance Line<br />

Motor protection<br />

Without (standard) 1) A – Only for: 1MB.5..<br />

Basic Line<br />

3 PTC thermistors – for tripping<br />

(2 terminals) 1) 2) 3) B – ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ Only for: 1MB.5..<br />

Basic Line<br />

Only for: MB.6..<br />

Performance Line<br />

6 PTC thermistors – for warning<br />

and tripping (4 terminals) 2) 3) C – ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓<br />

5<br />

1) For the Performance Line, motor protection by means of PTC thermistors<br />

with 3 built-in temperature sensors for tripping (motor protection code letter<br />

B) is already included in the basic price. For the Performance Line, the<br />

option "without motor protection" (motor protection code letter A) is not<br />

possible.<br />

2) Evaluation with associated tripping unit (see Catalog IC 10) is recommended.<br />

3) <strong>Motors</strong> in these frame sizes have a second rating plate (T1/T2 and T3) as<br />

standard.<br />

The T3 power is stamped on the rating plate as standard if the following<br />

motors are selected with PTC thermistor (protection by PTC thermistor<br />

only) or voltage code "90":<br />

– 2-pole motors: Frame sizes 132 to 160<br />

– 4-pole motors: Frame size 180<br />

Alternatively, with order code B33, the "T1/T2 power is stamped on the<br />

rating plate".<br />

– 2-pole motors: Frame sizes 132 to 200<br />

– 4-pole motors: Frame sizes 180 to 200<br />

5/70 Siemens D 81.1 · <strong>06</strong>/<strong>2020</strong>