7-3. Special Functions<br />
7-3-1. Noise Reducing Control (Outdoor Unit)<br />
The noise reducing control is the function used for silent operation of the <strong>air</strong> <strong>conditioner</strong> by means of<br />
setting the dip switch on the outdoor unit P.C.Board to control the fan and compressor's motor speed.<br />
NOTE<br />
When this function is used, the cooling or heating ability is slightly degraded. Therefore,<br />
when this function is to be enabled, make sure to receive the approval of the client.<br />
<br />
Specifications<br />
Noise Reducing Control<br />
(Fan's motor speed : 550rpm)<br />
Cooling Heating Cooling Heating<br />
50 dB-A 53 dB-A 47 dB-A 47 dB-A<br />
<br />
Outdoor Air Temp. [°C]<br />
33<br />
28<br />
NOTE<br />
Normal Operation<br />
Normal Operation or<br />
Noise Reducing Operation is kept.<br />
(Initial setting is the normal operation.)<br />
Noise Reducing Operation<br />
1. In the test operation, high-power operation, defrost operation or low ambient cooling<br />
operation (to be cancelled at the outside temperature of 14 °C or less, or 17 °C or<br />
more), the noise reducing control is not available.<br />
2. In the noise reducing operation, the fan's maximum motor speed is limited to 550rpm.<br />
Also, the maximum frequency (Hz) is controlled in the cooling (42Hz) or heating<br />
operation (40Hz).<br />
<br />
(1) Remove the 3 screws fixing the right front cover and remove the right front cover. (Fig. 2)<br />
(2) When the switch No. 1 of the dip switch (SW01) on the control P.C.Board is turned ON,<br />
the noise reducing control is enabled. (Fig. 3)<br />
Slide downward<br />
Fig.2 View from front<br />
Outdoor Air Temp. [°C]<br />
15<br />
10<br />
Control P.C.Board<br />
Right front cover<br />
24<br />
<br />
Noise Reducing Operation<br />
Normal Operation or<br />
Noise Reducing Operation is kept.<br />
(Initial setting is the normal operation.)<br />
ERR0<br />
ERR1<br />
ERR2<br />
ERR3<br />
Normal Operation<br />
Power lamp<br />
SW01<br />
SW02<br />
Fig.3 Control P.C.Board<br />
SW01<br />
ON<br />
1 2<br />
Dip switch (SW01)