7-3-2. Maximum Current Value Change Function<br />

The maximum current value is changed to 15.0A or 13.5A to prevent power breaker tripping.<br />

(It is set to 20A when the unit is delivered from the factory.)<br />

NOTE<br />

<br />

(1) Remove the right front cover.<br />

Refer to Fig. 2 in "7-3-1 Noise Reducing Control" for details.<br />

(2) When the switch No.1 of the dip switch (SW02) on the control P.C.Board is turned ON,<br />

the maximum current value change function is available. (Fig. 4)<br />

(3) Using the switch No.2 of the dip switch (SW02) on the control P.C.Board, the maximum current<br />

value is changed. (Fig. 4)<br />

Dip Switch<br />

SW02<br />

1. When the high load is given (Outside temperature is high in the cooling operation, or<br />

outdoor temperature is low in the heating operation), the capacity is reduced.<br />

When the maximum current value change function is to be enabled, make sure to receive<br />

the approval of the client.<br />

2. The maximum capacity for cooling or heating operation is about as much as the rated<br />

capacity.<br />

Description of function<br />

Frequency Current<br />

Target<br />

frequency<br />

Example of operation for heating<br />

Frequency<br />

Stops operation<br />

Approx.3 minutes<br />

ON<br />

OFF<br />

Max. Current Value<br />

13.5A<br />

15.0A<br />

Power Point C<br />

Point B<br />

Point A<br />

• Operates at the target frequency at Point A and below.<br />

• Stops increases to the frequency between Points A and B.<br />

• Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.<br />

•<br />

Stops operation, and restarts it appoximately 5 minutes later, if Point C is exceeded.<br />

(May operate when sudden voltage fluctuations occur. Indicates trouble.)<br />

ERR0<br />

ERR1<br />

ERR2<br />

ERR3<br />

Fig.4 Control P.C.Board<br />

25<br />

Power lamp<br />

SW01<br />

• In cooling or heating operation<br />

Max. Current Value 15.0A 13.5A<br />

Current Value<br />

on the Point B<br />

15.0A 13.5A<br />

Current Value<br />

on the Point A<br />

13.8A 12.3A<br />

SW02<br />

SW02<br />

ON<br />

1 2<br />

Dip switch (SW02)