7-3-2. Maximum Current Value Change Function<br />
The maximum current value is changed to 15.0A or 13.5A to prevent power breaker tripping.<br />
(It is set to 20A when the unit is delivered from the factory.)<br />
NOTE<br />
<br />
(1) Remove the right front cover.<br />
Refer to Fig. 2 in "7-3-1 Noise Reducing Control" for details.<br />
(2) When the switch No.1 of the dip switch (SW02) on the control P.C.Board is turned ON,<br />
the maximum current value change function is available. (Fig. 4)<br />
(3) Using the switch No.2 of the dip switch (SW02) on the control P.C.Board, the maximum current<br />
value is changed. (Fig. 4)<br />
Dip Switch<br />
SW02<br />
1. When the high load is given (Outside temperature is high in the cooling operation, or<br />
outdoor temperature is low in the heating operation), the capacity is reduced.<br />
When the maximum current value change function is to be enabled, make sure to receive<br />
the approval of the client.<br />
2. The maximum capacity for cooling or heating operation is about as much as the rated<br />
capacity.<br />
Description of function<br />
Frequency Current<br />
Target<br />
frequency<br />
Example of operation for heating<br />
Frequency<br />
Stops operation<br />
Approx.3 minutes<br />
ON<br />
OFF<br />
Max. Current Value<br />
13.5A<br />
15.0A<br />
Power Point C<br />
Point B<br />
Point A<br />
• Operates at the target frequency at Point A and below.<br />
• Stops increases to the frequency between Points A and B.<br />
• Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.<br />
•<br />
Stops operation, and restarts it appoximately 5 minutes later, if Point C is exceeded.<br />
(May operate when sudden voltage fluctuations occur. Indicates trouble.)<br />
ERR0<br />
ERR1<br />
ERR2<br />
ERR3<br />
Fig.4 Control P.C.Board<br />
25<br />
Power lamp<br />
SW01<br />
• In cooling or heating operation<br />
Max. Current Value 15.0A 13.5A<br />
Current Value<br />
on the Point B<br />
15.0A 13.5A<br />
Current Value<br />
on the Point A<br />
13.8A 12.3A<br />
SW02<br />
SW02<br />
ON<br />
1 2<br />
Dip switch (SW02)