8-2-2. Display of the Error Monitor Lamps<br />

ERROR MONITOR LAMP<br />

ERR0 ERR1 ERR2<br />

ERR3<br />

DIAGNOSTICS ITEM<br />

SENSOR FOR BRANCH PIPE A<br />

FAILURE (NARROW TUBE)<br />

SENSOR FOR BRANCH PIPE B<br />

FAILURE (NARROW TUBE)<br />

SENSOR FOR BRANCH PIPE C<br />

FAILURE (NARROW TUBE)<br />

SENSOR FOR BRANCH PIPE D<br />

FAILURE (NARROW TUBE)<br />

SENSOR FOR BRANCH PIPE E<br />

FAILURE (NARROW TUBE)<br />

SENSOR FOR BRANCH PIPE A<br />

FAILURE (WIDE TUBE)<br />

SENSOR FOR BRANCH PIPE B<br />

FAILURE (WIDE TUBE)<br />

SENSOR FOR BRANCH PIPE C<br />

FAILURE (WIDE TUBE)<br />

SENSOR FOR BRANCH PIPE D<br />

FAILURE (WIDE TUBE)<br />

SENSOR FOR BRANCH PIPE E<br />

FAILURE (WIDE TUBE)<br />

SENSOR FOR COMPRESSOR<br />

DISCHARGE TEMP FAILURE<br />

SENSOR FOR HEAT EXCHANGER<br />

TEMP FAILURE<br />

SENSOR FOR OUTDOOR AIR TEMP<br />

FAILURE<br />

HIC CIRCUIT TROUBLE<br />

ACTUATION OF FREEZE<br />

PROTECTION FUNCTION<br />

ACTUATION OF COMPRESSOR<br />

OVER LOAD RELAY<br />

ELECTRICAL CURRENT SENSOR<br />

FAILURE<br />

EXTERNAL ROM (OTP DATA)<br />

FAILURE<br />

PEAK CURRENT CUT-OFF<br />

PAM (PFC) CIRCUIT FAILURE<br />

COMPRESSOR DISCHARGE<br />

OVERHEAT PREVENTION ACTIVATED<br />

DC COMPRESSOR DRIVE FAILURE<br />

28<br />

(1) SENSOR OPEN CIRCUIT OR SHORT CIRCUIT<br />

(2) CONTACT FAILURE AT CONNECTOR OR OPEN CIRCUIT AT TERMINAL<br />

CRIMPING LOCATION<br />

(1) HIC OR POWER TR FAILURE (2) OUTDOOR FAN DOES NOT TURN<br />

(3) INSTANTANEOUS POWER OUTAGE (4) SERVICE VALVE NOT OPENED<br />

(5) OUTDOOR FAN FAILURE (6) CONTINUOUS OVER LOAD OPERATION<br />

(7) COMPRESSOR FAILURE (8) HIC BOARD FAILURE<br />

(1) SENSOR FAILURE (2) FAILURE OF ELECTRONIC EXPANSION VALVE<br />

(3) IMPROPER TUBING CONNECTION (4) CONTROL P.C.BOARD FAILURE<br />

(1) VALVE CLOSURE (2) FAILURE OF ELECTRONIC EXPANSION VALVE<br />

(3) OLR LEAD WIRE BREAKING (4) CONTROL P.C.BOARD FAILURE<br />

(1) CONTROL P.C.BOARD OR NOISE FILTER P.C.BOARD FAILURE<br />

(1) EXTERNAL ROM DATA FAILURE (2) CONTROL P.C.BOARD FAILURE<br />

(1) OPERATING CURRENT IS 23A OR HIGHER<br />

(1) PAM CIRCUIT ABNORMAL VOLTAGE<br />

(2) PROTECTION FOR CURRENT (3) HIC BOARD FAILURE<br />

(1) ELECTRONIC EXPANSION VALVE FAILURE (2) CAPILLARIES CHOKED<br />

(3) SHORTAGE OF REFRIGERANT<br />

(1) OPEN PHASE (2) COMPRESSOR FAILURE<br />

(3) CONTROL P.C.BOARD OR HIC BOARD FAILURE<br />

NO-REFRIGERANT PROTECTION (1) SERVICE VALVE NOT OPENED (2) SHORTAGE OF REFRIGERANT<br />

DC FAN MOTOR DRIVE FAILURE<br />

.... OFF .... Blinking .... Illuminated<br />

DIAGNOSTICS CONTENTS<br />

(1) CONTACT FAILURE AT CONNECTOR (2) FAN MOTOR FAILURE<br />

(3) CONTROL P.C.BOARD FAILURE<br />