■ Overview<br />
The Standard Chemical library is a function block library for the<br />
SIMATIC <strong>PCS</strong> 7 process control system, which can be used in<br />
process engineering across all sectors. This library enables you<br />
to perform a wide variety of automation tasks very effectively,<br />
while at the same time reducing the engineering work and thus<br />
the configuration costs. The SC library has already been successfully<br />
used in more than 100 plants.<br />
The SC library is integrated into the system environment of<br />
SIMATIC <strong>PCS</strong> 7. It contains function blocks for CFCs, OS faceplates,<br />
OS block symbols (user objects) and configuration wizards.<br />
An operating and signaling behavior with plant-specific selectable<br />
or deselectable block functions is implemented in the function<br />
blocks which are suitable for both continuous and batch processes.<br />
Function blocks which control units such as motors or<br />
valves have the "on-site operation" mode in addition to the automatic<br />
and manual modes. This enables units to be operated directly<br />
"on site" and displayed in the process control system.<br />
In the case of blocking signals, a distinction is made in the function<br />
blocks between interlocking, operating condition and release<br />
for energizing.<br />
All function blocks with the automatic operating mode also have<br />
the option of supporting a non-saving behavior for commands<br />
from the sequential function chart (SFC). A termination of the sequential<br />
control system therefore results in the automatic deactivation<br />
of the units.<br />
The faceplates are clearly designed, and all major block functions<br />
are integrated in the standard view. This guarantees simple<br />
and safe operation of the plant.<br />
The operating privileges can be assigned specifically to the process<br />
tags; even recently assigned authorization levels in the<br />
WinCC User Administrator can be included.<br />
For better arrangement of process tags or processing sequences<br />
it is possible to display comments relating to the process<br />
tags in the faceplates.<br />
Siemens provides a manufacturer’s declaration for the SC library<br />
in which compliance with quality assurance measures according<br />
to DIN EN ISO 9001:2000 as well as the existence of a lifecycle<br />
model according to GAMP 4 for the product development are<br />
certified. A component of this important quality proof is also the<br />
grading of the SC library into the GAMP software categories.<br />
Libraries/blocks/tools<br />
SC library: <strong>PCS</strong> 7 block library<br />
for technological functions<br />
■ Function<br />
The SC library offers blocks for the following functions:<br />
• Analog measure value monitoring<br />
• PID control<br />
• Proportioning<br />
• Valve control<br />
• Multiway valve<br />
• Motor with 1 control signal<br />
• Motor with 2 directions of rotation or speeds<br />
• Motor for frequency converter<br />
• Interlocking<br />
• Binary operating block<br />
• Analog and binary operating block<br />
• Message block<br />
• Counter block<br />
■ Selection and Ordering Data Order No.<br />
SC library<br />
Block library for SIMATIC <strong>PCS</strong> 7<br />
V5.x, V6.0 and V6.1; function<br />
blocks, OS faceplates, OS block<br />
symbols and wizards as well as<br />
electronic documentation on<br />
CD-ROM;<br />
single license for use on an<br />
AS 414, AS 416, AS 417,<br />
AS 414H or AS 417H automation<br />
system; 2 languages (German,<br />
English)<br />
• Runtime license (required for On request<br />
each AS system),<br />
contains block library and<br />
OS faceplates<br />
• Engineering license (required On request<br />
for each ES workstation), contains<br />
OS block symbols and<br />
wizards<br />
■ More information<br />
Siemens AG<br />
A&D B36<br />
Mannheim, Germany<br />
Phone: +49 621 456-2455<br />
Fax: +49 621 456-3311<br />
E-mail: SC-Bibliothek.AuD-Mhm@siemens.com<br />
Siemens <strong>ST</strong> <strong>PCS</strong> <strong>7.1</strong> · <strong>September</strong> <strong>2005</strong><br />
6/5<br />
6