Libraries/blocks/tools<br />

<strong>PCS</strong> 7 SOE: Function block for signal recording<br />

with 1 ms resolution<br />

■ Overview<br />

6/6<br />

Siemens <strong>ST</strong> <strong>PCS</strong> <strong>7.1</strong> · <strong>September</strong> <strong>2005</strong><br />

■ Function<br />

The SOE driver offers:<br />

• Individual messages<br />

Each change of status of the process signals is transmitted to<br />

the SIMATIC <strong>PCS</strong> 7 operator system with a resolution of 1 ms.<br />

• Double messages<br />

Defined states of 2 signals and intermediate states are signaled.<br />

• Fleeting indications<br />

Changes of state of the inputs from "0" to "1" are transmitted.<br />

• Bit pattern 8/16/24/32 bit<br />

Freely definable states of equipment can be recorded.<br />

• Transformer stages<br />

Defined and undefined states of transformer stage encoders<br />

are signaled.<br />

• Count values<br />

Up to 16 count values of the module can be read out.<br />

■ Selection and Ordering Data Order No.<br />

The function block <strong>PCS</strong> 7 SOE enables the SIMATIC <strong>PCS</strong> 7 pro- SICAM MCP (time synchroniza- 6MD1 010-0BA00<br />

cess control system to process events with a resolution of 1 ms. tion version)<br />

With the aid of this function block, externally time-stamped<br />

events are processed in the automation system and signaled in<br />

correct sequence to the operator system. If the connection to the<br />

Module for synchronization of<br />

SICAM DI32<br />

SICAM DI32<br />

operator system is faulty, the <strong>PCS</strong> 7 SOE can buffer as many as Input module for signal recording<br />

2000 messages by default. Additional 1927 messages can be<br />

buffered in an additional data block.<br />

The <strong>PCS</strong> 7 SOE function block requires the input module<br />

SICAM DI32 for the signal recording. The SICAM DI32 input<br />

• 24 ... 60 V<br />

• 110 ... 125 V<br />

Plustool<br />

6MD1 021-0AA00<br />

6MD1 021-0BA00<br />

On request<br />

modules are time-synchronized by means of an external<br />

Tool for hardware configuration of<br />

DCF 77/GPS receiver and the SICAM MCP synchronization<br />

module.<br />

the SICAM modules on CD-ROM<br />

incl. authorization<br />

In both the central unit and the expansion unit of a 41x automation<br />

system, as many as ten SICAM DI32 input modules can be<br />

operated.<br />

Driver block <strong>PCS</strong> 7 SOE<br />

for SIMATIC <strong>PCS</strong> 7 V5.x, V6.0<br />

and V6.1<br />

Single license Runtime for a<br />

6AT4 813-0CB05-0YA0 C)<br />

The <strong>PCS</strong> 7 SOE is configured using the CFC Editor of SIMATIC SICAM DI32 in a SIMATIC <strong>PCS</strong> 7<br />

<strong>PCS</strong> 7.<br />

automation system AS 41x<br />

C) Subject to export regulations AL: N, ECCN: EAR99S<br />

■ More information<br />

<strong>PCS</strong> 7 SOE<br />

Siemens AG<br />

A&D SE SH 6<br />

Phone: +49 911 750 9110<br />

Fax: +49 911 750 9105<br />

SICAM hotline<br />

Phone: +49 180 524 7000<br />

E-mail: ptd.support@siemens.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!