6<br />
Libraries/blocks/tools<br />
<strong>PCS</strong> 7 SOE: Function block for signal recording<br />
with 1 ms resolution<br />
■ Overview<br />
6/6<br />
Siemens <strong>ST</strong> <strong>PCS</strong> <strong>7.1</strong> · <strong>September</strong> <strong>2005</strong><br />
■ Function<br />
The SOE driver offers:<br />
• Individual messages<br />
Each change of status of the process signals is transmitted to<br />
the SIMATIC <strong>PCS</strong> 7 operator system with a resolution of 1 ms.<br />
• Double messages<br />
Defined states of 2 signals and intermediate states are signaled.<br />
• Fleeting indications<br />
Changes of state of the inputs from "0" to "1" are transmitted.<br />
• Bit pattern 8/16/24/32 bit<br />
Freely definable states of equipment can be recorded.<br />
• Transformer stages<br />
Defined and undefined states of transformer stage encoders<br />
are signaled.<br />
• Count values<br />
Up to 16 count values of the module can be read out.<br />
■ Selection and Ordering Data Order No.<br />
The function block <strong>PCS</strong> 7 SOE enables the SIMATIC <strong>PCS</strong> 7 pro- SICAM MCP (time synchroniza- 6MD1 010-0BA00<br />
cess control system to process events with a resolution of 1 ms. tion version)<br />
With the aid of this function block, externally time-stamped<br />
events are processed in the automation system and signaled in<br />
correct sequence to the operator system. If the connection to the<br />
Module for synchronization of<br />
SICAM DI32<br />
SICAM DI32<br />
operator system is faulty, the <strong>PCS</strong> 7 SOE can buffer as many as Input module for signal recording<br />
2000 messages by default. Additional 1927 messages can be<br />
buffered in an additional data block.<br />
The <strong>PCS</strong> 7 SOE function block requires the input module<br />
SICAM DI32 for the signal recording. The SICAM DI32 input<br />
• 24 ... 60 V<br />
• 110 ... 125 V<br />
Plustool<br />
6MD1 021-0AA00<br />
6MD1 021-0BA00<br />
On request<br />
modules are time-synchronized by means of an external<br />
Tool for hardware configuration of<br />
DCF 77/GPS receiver and the SICAM MCP synchronization<br />
module.<br />
the SICAM modules on CD-ROM<br />
incl. authorization<br />
In both the central unit and the expansion unit of a 41x automation<br />
system, as many as ten SICAM DI32 input modules can be<br />
operated.<br />
Driver block <strong>PCS</strong> 7 SOE<br />
for SIMATIC <strong>PCS</strong> 7 V5.x, V6.0<br />
and V6.1<br />
Single license Runtime for a<br />
6AT4 813-0CB05-0YA0 C)<br />
The <strong>PCS</strong> 7 SOE is configured using the CFC Editor of SIMATIC SICAM DI32 in a SIMATIC <strong>PCS</strong> 7<br />
<strong>PCS</strong> 7.<br />
automation system AS 41x<br />
C) Subject to export regulations AL: N, ECCN: EAR99S<br />
■ More information<br />
<strong>PCS</strong> 7 SOE<br />
Siemens AG<br />
A&D SE SH 6<br />
Phone: +49 911 750 9110<br />
Fax: +49 911 750 9105<br />
SICAM hotline<br />
Phone: +49 180 524 7000<br />
E-mail: ptd.support@siemens.com