attempted, but provided <strong>in</strong>accurate fuel temperature measurements due to the decreased<br />

thickness <strong>of</strong> the liquid layer, caus<strong>in</strong>g fuel puddles to form <strong>in</strong> some regions and an uneven<br />

liquid layer distribution. Initially, the fuel temperature set po<strong>in</strong>t was to be used as a<br />

variable <strong>in</strong> the matrix; however, fuel temperatures above 125°F were found to create<br />

vapor concentrations beyond the calibration range <strong>of</strong> the FID. Therefore, the fuel<br />

temperature set po<strong>in</strong>t was generally 30°F higher than the equilibrium fuel temperature, as<br />

it was found sufficient to demonstrate vapor evolution from a heated liquid without<br />

exceed<strong>in</strong>g the FID calibration range. Several experiments were performed for each<br />

location <strong>in</strong> the test matrix to verify the repeatability <strong>of</strong> the experiment.<br />

4.1 Constant Pressure Tests<br />

Table 4.1. Test Matrix<br />

Altitude<br />

Test Type: 0 10,000 20,000 30,000<br />

Const. P X X X X<br />

Vary T & P N/A X X X<br />

Isooctane X N/A N/A N/A<br />

Dry <strong>Tank</strong> X N/A N/A X<br />

The fuel was loaded <strong>in</strong>to the tank and allowed to equilibrate for at least 1-2 hours, as this<br />

length <strong>of</strong> time was determ<strong>in</strong>ed sufficient for equilibrium. Dur<strong>in</strong>g equilibration the heated<br />

l<strong>in</strong>es were switched on and the hydrocarbon analyzer was zeroed and calibrated with 2%<br />

and 4% propane mixtures. The fuel temperature set po<strong>in</strong>t was dialed <strong>in</strong>to the blanket<br />

heater temperature controller and the test-specific sett<strong>in</strong>gs were loaded <strong>in</strong>to the DAS.<br />

After sufficient time was allowed for equilibrium to be atta<strong>in</strong>ed, the DAS was set to beg<strong>in</strong><br />

sampl<strong>in</strong>g and the hydrocarbon analyzer sample location was switched from ambient air<br />

outside the chamber to <strong>in</strong>side the fuel tank. After a few m<strong>in</strong>utes <strong>of</strong> record<strong>in</strong>g temperature<br />

28