Travel position for slave in % if<br />

input “Master zero position command“ = 1<br />

0 … 100<br />

(Zero position sensor at input 4 <strong>of</strong> actuator)<br />

<strong>Actuator</strong> is<br />

Slave<br />

Transmission repetition for slave status in sec 1 … 255<br />

Monitoring period for master status in sec 1 … 255<br />

Travel position for slave in % if<br />

input “Master zero position command“ = 1<br />

0 … 100<br />

Monitoring <strong>of</strong> alarm and blocking objects<br />

If “Monitoring <strong>of</strong> alarm and blocking objects: Yes” has been selected:<br />

Monitoring period for<br />

5 sec … 2h<br />

alarm/blocking objects<br />

Behaviour in case <strong>of</strong> non-receipt <strong>of</strong> an<br />

alarm/blocking object<br />

Stop • <strong>UP</strong>-command • DOWN-command<br />

The priorities <strong>of</strong> the following functions correspond with the order in the programme!<br />

Note: Alarm and blocking objects block at 1<br />

Alarm object<br />

Use alarm object<br />

No • Yes<br />

If “Use alarm object: Yes“ has been selected:<br />

Use alarm object<br />

Yes<br />

If alarm object value = 1<br />

If alarm object value = 0<br />

In case <strong>of</strong> manual operation before and after<br />

alarm<br />

In case <strong>of</strong> automatic operation after alarm<br />

Value <strong>of</strong> the object before 1st communication<br />

and restoration <strong>of</strong> bus voltage<br />

no action • Stop •<br />

<strong>UP</strong>-command • DOWN-command<br />

no action • move to last position<br />

Follow automatic<br />

0 • 1<br />

Blocking object 1 / 2<br />

Use blocking object 1<br />

Use blocking object 2<br />

No • Yes<br />

No • Yes<br />

If “Use blocking object 1 / 2: Yes“ has been selected:<br />

Settings see ”Alarm object”<br />

Wind block<br />

Use wind block<br />

No • Yes<br />