<strong>Actuator</strong> push button<br />
For the “General settings“, “Input 1 / 2 / 3 / 4 as actuator push button“ has been<br />
selected.<br />
If monitoring periods or operation range limits are used, the operation with a push<br />
button is not possible in case <strong>of</strong> a bus voltage breakdown.<br />
Push button function<br />
Control mode<br />
Up • Down (blind)<br />
Up • Down • Up/Down (roller shutter)<br />
Retract • Extend • Retract/Extend (awning)<br />
Close • Open • Open/Close (window)<br />
• Standard<br />
• Standard inverted<br />
• Comfort mode<br />
• Dead man’s control<br />
Standard control mode<br />
In case <strong>of</strong> short actuation, the drive mechanism moves step-by-step and stops,<br />
respectively. In case <strong>of</strong> long actuation, the drive mechanism moves to the end position.<br />
Time between short and long in 0.1 sec 1 … 50<br />
53