No. Name Function Flags DP type<br />

21 Exterior temperature blocking object UINT1 Input C R W 1.003<br />

22 Exterior temperature block measured value UINT16 Input C R W 9.001<br />

23 Exterior temperature block status UINT1 Output C R T 1.002<br />

24 Dawn object UINT1 Input C R W 1.003<br />

25 Dawn measured value UINT16 Input C R W 9.004<br />

26 Dawn status UINT1 Output C R T 1.002<br />

27 Time control UINT1 Input C R W 1.002<br />

28 Inside temperature release object UINT1 Input C R W 1.003<br />

29 Inside temperature release measured value UINT16 Input C R W 9.001<br />

30 Inside temperature release target value UINT16 Input C R W 9.001<br />

31 Inside temperature release status UINT1 Output C R T 1.002<br />

32 Shading object UINT1 Input C R W 1.003<br />

33 Shading light measured value 1 UINT16 Input C R W 9.004<br />

34 Shading light measured value 2 UINT16 Input C R W 9.004<br />

35 Shading light measured value 3 UINT16 Input C R W 9.004<br />

36 Shading threshold UINT16<br />

Input/Output<br />

37 Shading threshold<br />

1 = Up / 0 = Down<br />

C R W T 9.004<br />

UINT1 Input C R W 1.007<br />

38 Shading threshold Up UINT1 Input C R W 1.017<br />

39 Shading threshold Down UINT1 Input C R W 1.017<br />

40 Shading status UINT1 Output C R T 1.002<br />

41 Shading position learning object UNIT1 Input C R W 1.017<br />

42 Azimuth UINT16 Input C R W 9.*<br />

43 Elevation UINT16 Input C R W 9.*<br />

44 Cold air supply blocking object UINT1 Input C R W 1.003<br />

45 Cold air supply outside temperature<br />

measured value<br />

UINT16 Input C R W 9.001<br />

46 Cold air supply block status UINT1 Output C R T 1.002<br />

47 Coercive ventilation UINT1 Input C R W 1.002<br />

48 Hot air supply blocking object UINT1 Input C R W 1.003<br />

49 Hot air supply inside temperature<br />

measured value<br />

50 Hot air supply outside temperature<br />

measured value<br />

UINT16 Input C R W 9.001<br />

UINT16 Input C R W 9.001<br />

51 Hot air supply block target value UINT16 Input C R W 9.001<br />

52 Hot air supply block status UINT1 Output C R T 1.002<br />