No. Name Function Flags DP type<br />
21 Exterior temperature blocking object UINT1 Input C R W 1.003<br />
22 Exterior temperature block measured value UINT16 Input C R W 9.001<br />
23 Exterior temperature block status UINT1 Output C R T 1.002<br />
24 Dawn object UINT1 Input C R W 1.003<br />
25 Dawn measured value UINT16 Input C R W 9.004<br />
26 Dawn status UINT1 Output C R T 1.002<br />
27 Time control UINT1 Input C R W 1.002<br />
28 Inside temperature release object UINT1 Input C R W 1.003<br />
29 Inside temperature release measured value UINT16 Input C R W 9.001<br />
30 Inside temperature release target value UINT16 Input C R W 9.001<br />
31 Inside temperature release status UINT1 Output C R T 1.002<br />
32 Shading object UINT1 Input C R W 1.003<br />
33 Shading light measured value 1 UINT16 Input C R W 9.004<br />
34 Shading light measured value 2 UINT16 Input C R W 9.004<br />
35 Shading light measured value 3 UINT16 Input C R W 9.004<br />
36 Shading threshold UINT16<br />
Input/Output<br />
37 Shading threshold<br />
1 = Up / 0 = Down<br />
C R W T 9.004<br />
UINT1 Input C R W 1.007<br />
38 Shading threshold Up UINT1 Input C R W 1.017<br />
39 Shading threshold Down UINT1 Input C R W 1.017<br />
40 Shading status UINT1 Output C R T 1.002<br />
41 Shading position learning object UNIT1 Input C R W 1.017<br />
42 Azimuth UINT16 Input C R W 9.*<br />
43 Elevation UINT16 Input C R W 9.*<br />
44 Cold air supply blocking object UINT1 Input C R W 1.003<br />
45 Cold air supply outside temperature<br />
measured value<br />
UINT16 Input C R W 9.001<br />
46 Cold air supply block status UINT1 Output C R T 1.002<br />
47 Coercive ventilation UINT1 Input C R W 1.002<br />
48 Hot air supply blocking object UINT1 Input C R W 1.003<br />
49 Hot air supply inside temperature<br />
measured value<br />
50 Hot air supply outside temperature<br />
measured value<br />
UINT16 Input C R W 9.001<br />
UINT16 Input C R W 9.001<br />
51 Hot air supply block target value UINT16 Input C R W 9.001<br />
52 Hot air supply block status UINT1 Output C R T 1.002<br />
8