06.03.2014 Views

Structure of Actuator KNX S-B4T-UP 230 V AC - IQmarket

Structure of Actuator KNX S-B4T-UP 230 V AC - IQmarket

Structure of Actuator KNX S-B4T-UP 230 V AC - IQmarket

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Control <strong>of</strong> windows<br />

For „General settings“, „<strong>Actuator</strong> controls window“ has been selected.<br />

Window drive mechanism<br />

This is to indicate the specific features <strong>of</strong> the connected drive mechanism.<br />

Exchange CLOSE/OPEN<br />

No • Yes<br />

Runtime OPEN in sec 0 … 320<br />

Runtime CLOSE in sec 0 … 320<br />

Pause time for direction change in 0.1 sec 0 … 100<br />

Accomplish reference run<br />

No • Yes<br />

Send drive position after change<br />

No • Yes<br />

If “Accomplish reference run: Yes“ has been selected:<br />

in case <strong>of</strong> more than<br />

1 … 255<br />

runs before one auto. position operation<br />

The reference run is always accomplished in the direction <strong>of</strong> the safe position.<br />

If “Send drive position after change: Yes” has been selected:<br />

Transmission delay <strong>of</strong> the position in 0.1 sec 0 … 50<br />