Dawn control / time control<br />

Use dawn and time control<br />

• No<br />

• only dawn control<br />

• only time control<br />

• both (OR gating)<br />

If dawn control or time control or both are used:<br />

Type <strong>of</strong> dawn input object<br />

1 Bit • 16 Bit<br />

If “Type <strong>of</strong> dawn input object 16 bit“ has been selected:<br />

Type <strong>of</strong> dawn input object<br />

16 Bit<br />

Dawn threshold value in lux 1 … 1000<br />

Switching delay<br />

1 minute<br />

Send current dawn status<br />

No • Yes<br />

Time control is accomplished by a communication object.<br />

Release <strong>of</strong> indoor temperature<br />

Use indoor temperature release<br />

No • Yes<br />

If “Use indoor temperature release: Yes“ has been selected:<br />

Type <strong>of</strong> input object<br />

1 bit • 16 bit • 16 bit target/actual temperature<br />

If “Type <strong>of</strong> input object 1 bit“ has been selected:<br />

Shading is permitted if bit is 1, and it is blocked if bit is 0.<br />

If “Type <strong>of</strong> input object 16 bit“ has been selected:<br />

Shading is permitted if the measured value is larger than or equal to the threshold, and<br />

it is blocked if the measured value is smaller than the threshold minus hysteresis.<br />

Threshold in 0.1°C -300 … 800<br />

Hysteresis in 0.1°C 1 … 100<br />

Send current block status<br />

No • Yes<br />

If “Type <strong>of</strong> input object 16 bit target/actual temperature“ has been selected:<br />

Shading is permitted if the measured value is larger than or equal to the target value<br />

plus the target-actual-difference, and it is blocked if the measured value is smaller than<br />

the target value plus the target-actual-difference minus hysteresis.<br />

The target value is provided by the communication object.<br />

Target-actual difference in 0.1 °C 1 … 100<br />

Hysteresis in 0.1°C 1 … 100<br />

Send current block status<br />

No • Yes<br />

Shading automatic<br />

Use shading automatic<br />

No • Yes<br />