Installation<br />
• Use the radiator key to unlock the two latches a quarter<br />
turn (fig. 7, pos. 1).<br />
• Open the latches (fig. 7, pos. 2).<br />
• Remove the casing by lifting it upwards and then pulling<br />
it forwards (fig. 7, pos. 3); do not hold the casing by the<br />
latches.<br />
• Hold the boiler by the rear boiler casing and place it on<br />
the wall bracket.<br />
3<br />
2<br />
2<br />
1<br />
• Level out the boiler.<br />
2<br />
2<br />
Fig. 7<br />
Removing the casing<br />
6.3 Making the gas connection<br />
DANGER<br />
Only carry out work on gas lines if you are<br />
licensed for such work.<br />
• Determine proper size gas pipe for the installation using<br />
see table 2 and see table 3. Do not forget the pipe fitting<br />
losses and observe proper size of the fittings.<br />
• Install the furnished ¾” gas cock on the gas connection.<br />
• Connect the gas pipe to the gas cock (fig. 8, pos. 1) so<br />
that it is free from any strain.<br />
1<br />
Fig. 8<br />
Making the gas connection<br />
NOTICE<br />
When installing the gas supply connection, it<br />
must comply with local regulations or, if such<br />
regulations do not exist, with the National Fuel<br />
Gas Code, ANSI Z 223.1.<br />
In Canada, the gas supply connection must<br />
comply with local regulations or, if such regulations<br />
do not exist, with CAN/CSA B149.1,<br />
Natural Gas and Propane Installation Code.<br />
A sediment trap must be provided upstream of the gas<br />
controls.<br />
Length of<br />
pipe (feet)<br />
Gas Volume Capacity<br />
(ft 3 / hr) 1<br />
¾" 1" 1 ¼" 1 ½"<br />
10 278 520 1,060 1,600<br />
20 190 350 730 1,100<br />
30 152 285 590 890<br />
40 130 245 500 760<br />
50 115 215 440 670<br />
75 93 175 360 545<br />
100 79 160 305 480<br />
150 64 120 250 380<br />
Table 2 Gas Pipe Capacity for different pipe sizes<br />
1 Maximum pipe capacity in ft 3 /hr, based on a specific gravity of<br />
.60 (42 mbar) and a inlet gas pressure of 14 inches W.C.<br />
(35 mbar) or less and a pressure drop of .3 inches W.C. (20 mbar)<br />