6<br />

Installation<br />

• Use the radiator key to unlock the two latches a quarter<br />

turn (fig. 7, pos. 1).<br />

• Open the latches (fig. 7, pos. 2).<br />

• Remove the casing by lifting it upwards and then pulling<br />

it forwards (fig. 7, pos. 3); do not hold the casing by the<br />

latches.<br />

• Hold the boiler by the rear boiler casing and place it on<br />

the wall bracket.<br />

3<br />

2<br />

2<br />

1<br />

• Level out the boiler.<br />

2<br />

2<br />

Fig. 7<br />

Removing the casing<br />

6.3 Making the gas connection<br />

DANGER<br />

Only carry out work on gas lines if you are<br />

licensed for such work.<br />

• Determine proper size gas pipe for the installation using<br />

see table 2 and see table 3. Do not forget the pipe fitting<br />

losses and observe proper size of the fittings.<br />

• Install the furnished ¾” gas cock on the gas connection.<br />

• Connect the gas pipe to the gas cock (fig. 8, pos. 1) so<br />

that it is free from any strain.<br />

1<br />

Fig. 8<br />

Making the gas connection<br />

NOTICE<br />

When installing the gas supply connection, it<br />

must comply with local regulations or, if such<br />

regulations do not exist, with the National Fuel<br />

Gas Code, ANSI Z 223.1.<br />

In Canada, the gas supply connection must<br />

comply with local regulations or, if such regulations<br />

do not exist, with CAN/CSA B149.1,<br />

Natural Gas and Propane Installation Code.<br />

A sediment trap must be provided upstream of the gas<br />

controls.<br />

Length of<br />

pipe (feet)<br />

Gas Volume Capacity<br />

(ft 3 / hr) 1<br />

¾" 1" 1 ¼" 1 ½"<br />

10 278 520 1,060 1,600<br />

20 190 350 730 1,100<br />

30 152 285 590 890<br />

40 130 245 500 760<br />

50 115 215 440 670<br />

75 93 175 360 545<br />

100 79 160 305 480<br />

150 64 120 250 380<br />

Table 2 Gas Pipe Capacity for different pipe sizes<br />

1 Maximum pipe capacity in ft 3 /hr, based on a specific gravity of<br />

.60 (42 mbar) and a inlet gas pressure of 14 inches W.C.<br />

(35 mbar) or less and a pressure drop of .3 inches W.C. (20 mbar)<br />

14<br />