11<br />

Inspection<br />

11.3 Internal leak testing<br />

• Switch off the heating system using the main switch.<br />

• Test for internal leaks of the gas burner fitting on the inlet<br />

side, applying a test pressure of 7.0 inch W.C.<br />

(17.4 mbar) in case of natural gas and 11.0 mbar<br />

(27.4 mbar) in case of LPG.<br />

After one minute the pressure must not have dropped by<br />

more than 3.8 inch W.C. (10 mbar).<br />

• If the pressure has dropped more, you must check all<br />

gaskets and joints upstream of the gas burner fitting for<br />

leaks using a foaming agent. Repeat the pressure test if<br />

no leaks are found. If the pressure has again dropped by<br />

more than 3.8 inch W.C. (10 mbar) per minute you will<br />

have to replace the gas burner fitting.<br />

11.4 Measuring the ionization current<br />

See subsection 8.12 "Measuring the ionization current",<br />

page 37.<br />

11.5 Measuring the inlet gas pressure<br />

See subsection 8.7 "Inlet gas pressure", page 33.<br />

11.6 Checking and adjusting the gas/air ratio<br />

See subsection 8.8 "Checking and adjusting the gas/air<br />

ratio", page 34.<br />

11.7 Carrying out a gas leak test in operating<br />

conditions<br />

See subsection 8.9 "Carrying out a leak test in operating<br />

conditions", page 36.<br />

11.8 Measuring the carbon monoxide content<br />

(CO)<br />

See subsection 8.10 "Measuring the carbon monoxide<br />

content (CO)", page 36.<br />

11.9 Carrying out a pressure test of the<br />

heating system<br />

See chapter 8 "Start-up procedure", page 30.<br />

11.10 Checking the functioning and the safety<br />

of the air intake and flue gas conduit<br />

See subsection 8.5 "Checking the combustion air/flue gas<br />

connection", page 32.<br />

11.11 Checking venting systems<br />

Check air intake and flue gas for obstruction or damage.<br />

48<br />

Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!