12<br />

Maintenance<br />

• Loosen both sets of retaining clips (fig. 44, pos. 4 and 5)<br />

of the burner cover and remove the burner cover with the<br />

fan unit and the gas burner fitting (fig. 45, pos. 1).<br />

• Remove the gas/air distributor plate (fig. 45, pos. 2), the<br />

orifice plate (GB142-24, GB142-30 and GB142-60 only,<br />

fig. 45, pos. 3) and the burner (fig. 45, pos. 4). Note that<br />

the orifice plate of the GB142-60 has a different shape.<br />

• Clean the gas/air distributor plate, the orifice plate<br />

(GB142-24, GB142-30 and GB142-60 only) and the<br />

burner using compressed air.<br />

1<br />

2<br />

3<br />

4<br />

• Remove the baffle plate and clean it using compressed<br />

air (fig. 46).<br />

Fig. 45<br />

Cleaning the burner cover, gas/air distributor plate,<br />

orifice plate and burner<br />

• Flush the heat exchanger with water.<br />

• Re-assemble all parts in reverse order of disassembly.<br />

NOTICE<br />

It is important to inspect and properly replace<br />

the rubber gaskets.<br />

Fig. 46<br />

Baffle plate<br />

• Switch on the heating system using the main switch.<br />

Fig. 47<br />

Cleaning the heat exchanger<br />

• Press the "Chimney Sweep" d button until the decimal<br />

point is displayed. Leave the boiler on for approx.<br />

10 minutes.<br />

50<br />

Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!