Start-up procedure<br />
• Push against the drawer (fig. 40) to close the control<br />
panel.<br />
8.13 Testing the Ignition Safety shut off<br />
device<br />
• Switch off the heating system using the main switch.<br />
• Disconnect the plug and socket connection of the monitoring<br />
cable.<br />
• Switch on the heating system using the main switch.<br />
• Press the "Chimney Sweep" d button and hold it (for<br />
approx. two seconds), until the display shows the<br />
decimal point.<br />
• Check if the boiler does one start-up attempt and three<br />
restart attampts.<br />
After each start-up attempt the boiler will signal a start-up<br />
failure. A "6A" code can be seen in the display.<br />
After the last start-up attempt, the boiler will lock out. The<br />
"6A" code is blinking in the display.<br />
• Connect the plug and socket connection of the monitoring<br />
cable.<br />
• Press the reset button.<br />
• Check if the boiler starts-up.<br />
• Press the "Chimney Sweep" button return to normal<br />
operating conditions.<br />
Fig. 40<br />
Closing the control panel<br />
8.14 Installing the casing<br />
• Install the casing and close the latches (fig. 41).<br />
Do not lift the casing by the latches!<br />
• Lock the latches using the radiator key.<br />
8.15 Informing the owner, handing over the<br />
technical documents<br />
• Show the owner how the heating system works and how<br />
the boiler can be operated. Hand over the technical<br />
documents.<br />
Fig. 41<br />
Installing the casing<br />